2. Analogue input 2 (
AI2
):
Parameter
M10
=0
Remote control
sensor for zone 1
Sensor
AI2
is used as a control sensor for zone 1.
M10
=1
Remote control
sensor for zone 2
Sensor
AI2
is used as a control sensor for zone 2.
M10
=2
Remote control
sensor for zone 3
Sensor
AI2
is used as a control sensor for zone 3.
M10
=3
Remote control
sensor for zone 4
Sensor
AI2
is used as a control sensor for zone 4.
M10
=4
External sensor
Sensor
AI2
is used as an external sensor for control with compensation
M10
=5
Floor sensor for
zone 1
The
AI2
VHQVRULVXVHGDVÀRRUWHPSHUDWXUHPHDVXUHPHQWVHQVRUIRU]RQH
M10
=6
Floor sensor for
zone 2
The
AI2
VHQVRULVXVHGDVÀRRUWHPSHUDWXUHPHDVXUHPHQWVHQVRUIRU]RQH
M10
=7
Floor sensor for
zone 3
The
AI2
VHQVRULVXVHGDVÀRRUWHPSHUDWXUHPHDVXUHPHQWVHQVRUIRU]RQH
M10
=8
Floor sensor for
zone 4
The
AI2
VHQVRULVXVHGDVÀRRUWHPSHUDWXUHPHDVXUHPHQWVHQVRUIRU]RQH
M10
=9
Remote season
changeover contact
M11
=
0
1
Summer
Winter
M10
=10
Remote on/off
M11
=
0
1
On
Off
M10
=11
Non-occupied
holiday
M11
=
0
1
“Non-occupied holiday” mode
Occupied mode
M10
=12
Economy mode
M11
=
0
1
No economy mode
Economy mode
M10
=13
The
AI2
sensor is used for the dew point calculation (only for the
MASTER or SLAVE_Y controller)
M10
=14
The
AI2
sensor is used as limit sensor for the MASTER or SLAVE:Y
controller
M10
=15
Sensor not used
)RUFRQ¿JXUDWLRQV
M10
=9, 10, 11, 12, the analogue input 2 is used as a digital input. The contact is considered closed
if there is a short-circuit on the analogue input. The contact is considered open if there is no connection.