Registers
Description
Default
Min
Max.
R/W
7509
SET_LIM_HIGH
(see table pag.
40
) (°C [°F])
(Note1)
I35
300 [86]
I33
500 [122]
R/W
7510
PROP_BAND_LIM
(see table pag.
40
)
ǻ&>ǻ)@
(Note1)
I36
20 [36]
10 [18]
200 [360]
R/W
7511
AUTHORIZE_FLOOR_CTRL_ZONE_1
(see table pag.
40
)
0=Floor temperature not controlled
1=Limit control with room sensor control
2=Limit control, room sensor control excluded
I37
0
0
2
R/W
7512
AUTHORIZE_FLOOR_CTRL_ZONE_2
(see table pag.
40
)
0=Floor temperature not controlled
1=Limit control with room sensor control
2=Limit control, room sensor control excluded
I38
0
0
2
R/W
7513
AUTHORIZE_FLOOR_CTRL_ZONE_3
(see table pag.
40
)
0=Floor temperature not controlled
1=Limit control with room sensor control
2=Limit control, room sensor control excluded
I39
0
0
2
R/W
7514
AUTHORIZE_FLOOR_CTRL_ZONE_4
(see table pag.
40
)
0=Floor temperature not controlled
1=Limit control with room sensor control
2=Limit control, room sensor control excluded
I40
0
0
2
R/W
7515
SET_MIN_FLOOR_HEAT
(°C [°F])
(Note1)
I41
150 [59]
15 [59]
350 [95]
R/W
7516
SET_MAX_FLOOR_HEAT
(°C [°F])
(Note1)
I42
320 [90]
15 [59]
350 [95]
R/W
7517
HYST_FLOOR
(see table pag.
40
)
ǻ&>ǻ)@
(Note1)
I43
5 [9]
2 [4]
20 [36]
R/W
7518
AUTHORIZE_DEW_POINT_CTRL
(see table pag.
40
)
0=Not enabled
1=Dew point controller activation with humidity sensor in the appliance for
zone 1
2=Dew point controller activation with humidity sensor in the appliance for
zone 2
3=Dew point controller activation with humidity sensor in the appliance for
zone 3
4=Dew point controller activation with humidity sensor in the appliance for
zone 4
5=Dew point controller activation with humidity sensor in the appliance for the
MASTER or SLAVE_Y controller
6=Dew point controller activation with remote humidity sensor in the appliance
for zone 1
7=Dew point controller activation with remote humidity sensor in the appliance
for zone 2
8=Dew point controller activation with remote humidity sensor in the appliance
for zone 3
9=Dew point controller activation with remote humidity sensor in the appliance
for zone 4
10=Dew point controller activation with remote humidity sensor in the appli-
ance for the MASTER or SLAVE_Y controller
I44
0
0
10
R/W
7519
OFFSET_DEW_POINT_CTRL
(see table pag.
40
)
ǻ&>ǻ)@
(Note1)
.
I45
20 [36]
-100 [-180]
100 [180]
R/W
7520
STATE_LOC_PUMP_IN_ALARM
(see table pag.
40
)
0=Circulator and valve switched off in case of condensation or dew point
alarm
1=Circulator and valve switch on in case of condensation or dew point alarm
I46
1
0
1
R/W
7521
TEMP_EXT_MIN_HEAT
(see table pag.
40
) (°C [°F])
(Note1)
I47
-100 [140]
-100 [140]
I48
R/W
7522
TEMP_EXT_MAX_HEAT
(see table pag.
40
) (°C [°F])
(Note1)
I48
200 [68]
I47
500 [122]
R/W
7523
SET_TEXT_MIN_HEAT
(see table pag.
40
) (°C [°F])
(Note1)
I49
350 [95]
50 [41]
800 [176]
R/W
7524
SET_TEXT_MAX_HEAT
(see table pag.
40
) (°C [°F])
(Note1)
I50
280 [82]
50 [41]
800 [176]
R/W
7525
TEMP_EXT_MIN_COOL
(see table pag.
40
) (°C [°F])
(Note1)
I51
240 [75]
-100 [140]
I52
R/W
7526
TEMP_EXT_MAX_COOL
(see table pag.
40
) (°C [°F])
(Note1)
I52
350 [95]
I51
500 [122]
R/W
7527
SET_TEXT_MIN_COOL
(see table pag.
40
) (°C [°F])
(Note1)
I53
200 [68]
50 [41]
800 [176]
R/W
7528
SET_TEXT_MAX_COOL
(see table pag.
40
) (°C [°F])
(Note1)
I54
160 [61]
50 [41]
800 [176]
R/W
7529
AUTHORIZE_DEHUMIDIFICATION
(see table pag.
40
)
0=Not enabled
1=Enabled with internal humidity sensor
2=Enabled with remote humidity sensor
3=Enabled with internal humidity sensor only in summer operation
4=Enabled with remote humidity sensor only in summer operation
I55
0
0
4
R/W
7530
SETPOINT_DEHUMIFICATION
(see table pag.
40
)
I56
500
0
1000
R/W
7531
PROP_BAND_DEHUMIDIFICATION
(see table pag.
40
)
I57
50
10
1000
R/W
7532
HYST_FAN_1
(see table pag.
40
)
ǻ&>ǻ)@
(Note1)
I58
10 [18]
2 [4]
50 [90]
R/W
7533
HYST_FAN_2
(see table pag.
40
)
ǻ&>ǻ)@
(Note1)
I59
10 [18]
2 [4]
50 [90]
R/W
7534
DIFF_S1_S2
(see table pag.
40
)
I60
2 [4]
2 [4]
50 [90]
R/W
7535
DIFF_S2_S3
(see table pag.
40
)
I61
2 [4]
2 [4]
50 [90]
R/W