Registers
Description
Min
Max.
R/W
8050
FLAG_LIM_ALARM
o
limit alarm status (at the SLAVE_Y controller)
0=No limit alarm
1=Upper heating limit exceeded, pre-alarm
2=Upper heating limit exceeded, alarm
3=Lower cooling limit exceeded
4=Lower cooling limit exceeded, alarm
0
4
R
8051
FLAG_ALARM_HIGH_CONTACT
o
KLJKWHPSHUDWXUHDODUPIURPDGLJLWDOFRQWDFWFRQ¿JXUHGDV
high temperature alarm (
M04
=7 or
M06
=7)
0=No high temperature alarm
1=High temperature alarm
0
1
R
8052
FLAG_ALARM_CONDENSATION
0=
No condensation alarm
1=Condensation alarm
0
1
R
8053
FLAG_ALARM_TSUPPLY_TOO_LOW
0=No alarm for supply temperature lower than the [Dew se Dew offset I45]
1=Alarm for supply temperature lower than the [Dew se Dew offset
I45
]
0
1
R
8054
FLAG_ALARM_DEW_POINT
0=No alarm for temperature lower than the [Dew se Dew offset I45]
1=Alarm for temperature lower or equal to the [Dew se Dew offset
I45
]
0
1
R
8055
FLAG_GEN_ALARM
0=No alarm
1=General alarm
0
1
R
8056
FLAG_DIRTY_FILTER_1
0=Clean
¿OWHURI
zone 1 fan coil
1=Dirty
¿OWHURI
zone 1 fan coil
0
1
R
8057
FLAG_DIRTY_FILTER_2
0=Clean
¿OWHURI
zone 2 fan coil
1=Dirty
¿OWHURI
zone 2 fan coil
0
1
R
8058
FLAG_STATE_DEHUMIDIFICATOR
'HKXPLGL¿HURII
'HKXPLGL¿HURQ
0
1
R
8059
FLAG_DESTRAT_1
)DQFRLOGHVWUDWL¿FDWLRQF\FOHQRWUXQQLQJ
)DQFRLOGHVWUDWL¿FDWLRQF\FOHUXQQLQJ
0
1
R
8060
FLAG_DESTRAT_2
)DQFRLOGHVWUDWL¿FDWLRQF\FOHQRWUXQQLQJ
)DQFRLOGHVWUDWL¿FDWLRQF\FOHUXQQLQJ
0
1
R
from 8061
to 8094
Reserved registers
R
8095
FORCED_OUTPUTS_KEY
o
key for forced outputs selection
0 / 26112
26367
R/W
8096
MASTER_WR_ON_OFF
o
ON/OFF status reveived from the MASTER controller
0=OFF
1=ON
0
1
R
8097
MASTER_WR_EXT_TEMP
o
temperature of the external sensor connected to the
MASTER (°C [°F])
(Note1)
-150 [5]
900 [195]
R
8098
MASTER_WR_SEASON
o
season received from the MASTER controller
0=Heating
1=Cooling
0
1
R
8099
MASTER_WR_SUPPLY_T
o
temperature of the supply sensor of the MASTER(°C [°F])
(Note1)
-150 [5]
900 [195]
R
8100
MASTER_WR_ALARM_DEWPOINT
o
dew point alarm received from the MASTER controller
0=No alarm
1=Alarm active
0
1
R
8101
MASTER_WR_ALARM_CONDENS
o
condensation alarm received from the MASTER controller
0=No alarm
1=Alarm active
0
1
R
8102
MASTER_WR_ALARM_GEN
o
general alarm received from the MASTER controller
0=No alarm
1=Alarm active
0
1
R
8103
MASTER_WR_ALARM_LIM
o
limit alarm received from the MASTER controller
0=No limit alarm
1=Upper heating limit pre-alarm
2=Upper heating limit alarm
3=Lower cooling limit pre-alarm
4=Lower cooling limit alarm
0
4
R
8104
MASTER_WR_ALARM_TEMP_CT
o
upper limit alarm from contact received from the MASTER
controller
0=No alarm
11=Alarm active
0
11
R