8.
Jumper configuration
General jumper configuration
The 10 I/Os Digital Module provide 10 digital pins that can act as both input and output. However, they
can only be working as one option at a time, so if their function is wished to be changed the jumpers
must be adjusted. The board is divided in four zones for controlling the I/Os pins, the GND and the I/Os
voltages. Also, the I/Os pins are divided in two blocks (0.9 to 0.5 and 0.4 to 0.0) that must be supplied
with the same voltage. In order to configure the pins properly, all the zones of the same pin must be set
correctly following the succeeding tables.
Warning!
If a pin is supplied with AC voltage, the entire block must be supplied with the same
voltage type. In the same way, if a pin is supplied with DC voltage, the entire block
must be supplied with DC voltage.
This jumper zone makes the selection between using the pins as
Inputs
or
Outputs
. There is a
Jumper Zone 1
with three pins on each side of
the board. In the case of using the pins as
Inputs,
the jumper must be
connected on the pins 1 and 2. Otherwise, if the pin is wished to work
as an
Output
, connect it on the pins 2 and 3. Both zones must be
connected on the same way in order to work properly. See an example
on the
section 8.2
.
The Jumper Zone 2 is for choosing between the board ground and an
external one. If the Board GND is chosen using the pins 2 and 3, the pin
will work using the common ground of the device. In the case of using
and external ground, set the jumper on the left side connecting it to
the pins 1 and 2. See an example on the
section 8.2
.
These jumpers have to be set depending on the alimentation that the
circuit is supplied with. If a power supply voltage of between 3V - 24V
is being used, the switch must be connected as the
Jumper Zone 3
photo. In the case of a 230 V power supply then the jumper must not
be connected. See an example on the
section 8.2
.
JUMPER ZONE 1
LEFT
RIGHT
1 2
3
1 2
3
IN - OUT
IN - OUT
JUMPER ZONE 2
External GND
Board GND
1 2
3
1
2 3
JUMPER ZONE 3
WITHOUT
WITH
230 V
3.3
– 24 V
Summary of Contents for PLC 10
Page 1: ...PLC 10 I Os DIGITAL MODULE CPU ARDUINO NANO PLC 10 I Os DIGITAL MODULE CPU ARDUINO NANO...
Page 2: ...Ref 013001000100 Rev 1 18 01 2021 1...
Page 25: ...Ref 013001000100 Rev 1 18 01 2021 24...
Page 30: ...Ref 013001000100 Rev 1 18 01 2021 29 10 Typical Connections 3 3 24v...
Page 32: ...Ref 013001000100 Rev 1 18 01 2021 31 12 10 I Os Family Dimensions 45mm width DIN rail mounting...