Ref. 004001001200
Rev.3: 17-01-2021
21
8.
Switch configuration
General Switches Configuration
LEFT ZONE SWITCH
Communications and inputs/outputs cannot work simultaneously.
6. I0.8 / RS-485 DE
–
If this switch is ON the RS-485 DE is activated, otherwise the I0.8 will be
activated.
5. RS-485 DE / I0.8
–
If this switch is ON the I0.8 is activated, otherwise the RS-485 DE will be
activated.
Note* To work with RS-485 DE, switch number 6 at ON and number 5 at OFF.
4. I0.9 / RS-485 RE
–
If this switch is ON the RS-485 RE is activated, otherwise the I0.9 will be
activated.
3. RS-485 RE / I0.9
–
If this switch is ON the I0.9 is activated, otherwise the RS-485 RE will be
activated.
Note* To work with RS-485 RE, switch number 4 at ON and number 3 at OFF.
2. SDA-D2/I0.0
–
If this switch is ON the I0.0 is activated, otherwise the (I2C) SDA-D2 will be
activated.
1. SCL-D3/Q0.6
–
If this switch is ON the (I2C) SCL-D3 is activated, otherwise the (I2C) SDA-D2
will be activated.
LEFT ZONE
SWITCH
OFF
ON
I0.8 / RS-485 DE
I0.8
RS-485 DE
RS-485 DE / I0.8 RS-485 DE
I0.8
I0.9 / RS-485 RE
I0.9
RS-485 RE
RS-485 RE / I0.9 RS-485 RE
I0.9
SDA-PIN2 / I0.0
SDA-D2
I0.0
SCL-PIN3 / Q0.6
SCL-D3
Q0.6
Summary of Contents for DALI 20
Page 2: ...Ref 004001001200 Rev 3 17 01 2021 1...
Page 31: ...Ref 004001001200 Rev 3 17 01 2021 30 PWM Waveform Analog Out Turn on Analog Out Turn off...
Page 33: ...Ref 004001001200 Rev 3 17 01 2021 32 13 Typical Connections...
Page 34: ...Ref 004001001200 Rev 3 17 01 2021 33...
Page 35: ...Ref 004001001200 Rev 3 17 01 2021 34...
Page 36: ...Ref 004001001200 Rev 3 17 01 2021 35...
Page 38: ...Ref 004001001200 Rev 3 17 01 2021 37 15 ARDBOX Family Dimensions 45mm width DIN rail mounting...