EK-WL8-TRH/AU
WIRELESS TRANSLATOR
MODULE
STFV.425551.070-AU-UM rev. 4
20.08.2020
Page 18 of 22
Configuration
Maintenance
Radio
Start Addr
Loop
Info
001wl8-o
Edit
Alarm sound
Alarm mess.
Message 2
Message 3
Message 1
Pulse 1s/1s
Pulse 2s/2s
Cont. tone
Dual 1s/1s
Dual .4s/.4s
Pulse .2s/1.3s
Tamper
Enabled
000wl8-trh
--ADD NEW--
WL8-TRH
v x.x/RF v.y
A1
)
Parameter
Value
Description
Alarm
sound
Cont. tone
Operation mode of the
siren in case of fire of
the child device which
has a siren
Continuous one tone
Pulse 1s/1s
1s
–ON /1s-OFF
Pulse 2s/2s
2s
–ON /2s-OFF
Dual 1s/1s
1s
–ON Tone1 /1s-ON Tone2
Dual .4s/.4s
0,4s
–ON Tone1 /0,4s-ON
Tone2
Pulse
.2s/1.3s
0,2s
–ON /1,3s-OFF
Alarm
mess.
Message 1
Variant of the pre-recorded voice message in the voice
annunciator (like WL8-V, WL8-OV) in case of fire
Message 2
Message 3
NOTE
The tone frequency depends on the type of siren and is showed in
the siren and combined devices user manuals.
Operation mode of all sirens in case of fire is selected in the settings of the
WL8-TRH (menu: Alarm sound) with the highest priority in relation to the
mode that is set in the options of the siren itself (menu: Sound for self-fire).
Effect of the "sound alarm" parameter on the WL8-SND tones.
Sound
alarm pa-
rameter
Switches condition on WL8-SND PCB (LEFT-RIGHT)
1(OFF) - 1(OFF) 1(OFF) - ON
ON
– 1 (OFF)
ON - ON
Cont. tone
Continuous tone
990Hz
Continuous
tone
990Hz
Unsynchronized
Dual tone
990Hz&650Hz
(250ms~250ms)
Unsynchronized
Pulsed tone
990Hz (500ms
On/500ms Off)
Pulse 1s/1s
Pulsed tone
(synchronized)
990Hz (1s
On/1s Off)
Pulse 2s/2s
Dual 1s/1s
Dual .4s/.4s
Pulse
.2s/1.3s
Summary of Contents for ekho EK-WL8-AU
Page 1: ...EK WL8 TRH AU WIRELESS TRANSLATOR MODULE STFV 425551 070 AU UM rev 4 20 08 2020 Page 1 of 22 ...
Page 6: ...EK WL8 TRH AU WIRELESS TRANSLATOR MODULE STFV 425551 070 AU UM rev 4 20 08 2020 Page 6 of 22 ...
Page 22: ...EK WL8 TRH AU WIRELESS TRANSLATOR MODULE STFV 425551 070 AU UM rev 4 20 08 2020 Page 22 of 22 ...