European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e-2-s.com             Fax: +44 (0)208 740 4200 
Document No. IS 2451-P       Issue E     19-02-10                                    Sheet 4 of 4                                                                                                  (4) 

care should be taken to dress the wire so that when the cover 
is  inserted  into  the  chamber  the  wires  do  not  exert  excess 
pressure on  the  terminal blocks. This is  particularly  important 
when  using  cables  with  large  cross  sectional  areas  such  as 
2.5mm² and above. 

 

 

13) 

 Tone Selection and 2nd and 3rd Stage Alarms

 

The BExDS120D and BExDS110D sounders have 32 different 
tones  that  can  be  selected  for  the  first  stage  alarm.  The 
sounders  can  then  be  switched  to  sound  second  and  third 
stage  alarm  tones.  The  tones  are  selected  by operation  of a 
DIP  switch  on  the  pcb  for  both  DC  and  AC  units.  The  tone 
table on page four shows the switch positions for the 32 tones 

and which tones are available for the second and third stages. 
To  operate  the  sounder  on  stage  one  simply  connect  the 
supply voltage to the normal supply terminals (+ve and –ve for 
DC units, L and N for AC units).  
 
The operation of the second and third stages is different for DC 
and AC units. 
 
DC Units Second and Third Stage Tone Selection 
The  BExDS120D  and  BExDS110D  DC  sounders  have  the 
facility to use ve or –ve switching to change the tone to 
the second and third stages. For –ve switching connect the two 
headers  on  the pcb to  the  left-hand  (marked –ve) and centre 

pins. For +ve switching connect the headers to the right hand 
(marked  +ve)  and  the  centre  pins.  To change to  the  second 
stage tone, connect either a -ve or +ve supply line to terminal 
S2,  depending on  which switching  mode  is  being  used  while 
maintaining  the  dc  supply  to  the  +ve  and  –ve  terminals. 
Similarly for the third stage tone, connect a -ve or +ve supply 
line  to  terminal  S3.  The  supply  to  the  S3  terminal  will 

automatically override a supply to the S2 terminal. 
 

AC Units Second and Third Stage Tone Selection 
To select the second and third stage tones on the BExDS120D 
and  BExDS110D  AC sounders  the  Common  (C)  terminal  on 
the three way terminal block on the pcb is connected to the S2 
terminal for the second stage tone and the S3 terminal for the 

third stage tone. 

 

14) 

 Volume Control

 

All BExDS120D and BExDS110D sounders, with the exception 
of 12V DC units,  have  a  volume control  to  adjust the  output 
level. To set the required output level, adjust the potentiometer 

on  the  pcb.  For  maximum  output  level  the  potentiometer 
should be set to the fully clockwise position. 
 

15) 

 End of Line Monitoring (DC Units)

 

On  BExDS120D  and  BExDS110D  DC  units,  dc  reverse  line 
monitoring  can  be  used if  required.  All  DC  sounders  have a 
blocking diode fitted in their supply input lines. An end of line 
monitoring  diode or an  end  of  line  monitoring  resistor can  be 
connected across the +ve and –ve terminals. If an end of line 
resistor  is  used it  must  have  a  minimum resistance  value  of 
3k3 ohms and a minimum wattage of 0.5 watts or a minimum 
resistance value of 500 ohms and a min. wattage of 2 watts. 

 

TONE SELECTION TABLE   

Note Switch No. 6 is not used 

 

 

 

Tone Selection 

 
DIP Switch                                    

Settings 

 
Stage Selection 

Stage 1 

Frequency Description 

1    2   3   4   5 

 

Stage 2 

Stage 3 

Continuous  1000Hz  

Toxic gas alarm 

0    0   0   0   0 

Tone 31 

Tone 11 

Alternating  800/1000Hz  at  0.25s 

intervals 

1    0   0   0   0 

Tone 17 

Tone 5 

Slow  Whoop  500/1200Hz  at  0.3Hz 

with 0.5s gap repeated 

0    1   0   0   0 

Tone 2 

Tone 5 

Sweeping 800/1000 at 1Hz 

1    1   0   0   0 

Tone 6 

Tone 5 

Continuous at 2400Hz 

0    0   1   0   0 

Tone 3 

Tone 27 

Sweeping 2400/2900Hz at 7Hz 

1    0   1   0   0 

Tone 7 

Tone 5 

Sweeping 2400/2900Hz at 1Hz 

0    1   1   0   0 

Tone 10 

Tone 5 

Siren 500/1200/500Hz at 0.3Hz 

1    1   1   0   0 

Tone 2 

Tone 5 

Sawtooth 1200/500Hz at 1Hz 

0    0   0   1   0 

Tone 15 

Tone 2 

10 

Alternating 2400/2900Hz at 2Hz 

1    0   0   1   0 

Tone 7 

Tone 5 

11 

Intermittent  1000Hz  at  0.5Hz 

General alarm

 

0    1   0   1   0 

Tone 31 

Tone 1 

12 

Alternating 800/1000Hz at 0.875Hz 

1    1   0   1   0 

Tone 4 

Tone 5 

13 

Intermittent 2400Hz at 1Hz 

0    0   1   1   0 

Tone 15 

Tone 5 

14 

Intermittent 800Hz 0.25s on 1s off 

1    0   1   1   0 

Tone 4 

Tone 5 

15 

Continuous at 800Hz 

0    1   1   1   0 

Tone 2 

Tone 5 

16 

Intermittent  660Hz  150mS  on, 

150mS off 

1    1   1   1   0 

Tone 18 

Tone 5 

17 

Alternating 544Hz  

(100mS)/440Hz(400mS) 

0    0   0   0   1 

Tone 2 

Tone 27 

18 

Intermittent 660Hz 1.8s on, 1.8s off 

1    0   0   0   1 

Tone 2 

Tone 5 

19 

1400Hz  to  1600Hz  sweep  up over 

1s - 1600Hz to 1400Hz sweep down  
over 0.5s 

0    1   0   0   1 

Tone 2 

Tone 5 

20 

Continuous 660Hz  

1    1   0   0   1 

Tone 2 

Tone 5 

21 

Alternating 554/440Hz at 1Hz 

0    0   1   0   1 

Tone 2 

Tone 5 

22 

Intermittent 554Hz at 0.875Hz 

1    0   1   0   1 

Tone 2 

Tone 5 

23 

800Hz pulsing at 2Hz 

0    1   1   0   1 

Tone 6 

Tone 5 

24 

Sweeping 800/1000Hz at 50Hz 

1    1   1   0   1 

Tone 29 

Tone 5 

25 

Sweeping 2400/2900Hz at 50Hz 

0    0   0   1   1 

Tone 29 

Tone 5 

26 

Simulated bell sound 

1    0   0   1   1 

Tone 2 

Tone 1 

27 

Continuous 554Hz 

0    1   0   1   1 

Tone 26 

Tone 5 

28 

Continuous 440Hz 

1    1   0   1   1 

Tone 2 

Tone 5 

29 

Sweeping 800/1000Hz at 7Hz 

0    0   1   1   1 

Tone 7 

Tone 5 

30 

420Hz repeating 0.625s on, 0.625s 

off  

Australian alert signal

 

1    0   1   1   1 

Tone 32 

Tone 5 

31 

1200/500Hz at 1 Hz  

Prepare to abandon platform 

0    1   1   1   1 

Tone 11 

Tone 1 

32 

Sweeping 500/1200Hz 3.75s on, 

0.25s off 15Hz 

1    1   1   1   1 

Tone 26 

Tone 1 

 

Figure 7 

Figure 6 

BExDS110D  DC Sounder 

BExDS110D  AC 
Sounder 

Volume Control 

DIP Switch 

DIP Switch 

Volume Control 

DC Terminals 

Stage Headers 

Stage Terminals 

AC Terminals 

 
S2 
S3

 


+

 

       S2 
       S3 

        C  
 
 
        N  
        L

 

Summary of Contents for BExDS110D

Page 1: ...ERE IS PRESENT COVER BOLTS CLASS A4 80 USE HEAT RESISTING CABLES AND CABLE GLANDS Rated 110ºC AT AMB TEMPERATURES OVER 40ºC Year of Construction Serial No i e 10 1DS22000001 3 Type Approval Standards The sounders have EC Type Examination and IECEx certificates issued by KEMA and have been approved to the following standards EN60079 0 2006 IEC60079 0 2004 Ed4 General Requirements EN60079 1 2007 IEC...

Page 2: ...in a safe place during installation On completion of the cable wiring installation the flameproof joints should be inspected to ensure that they are clean and that they have not been damaged during installation Also check that the earth bonding wire between the two casting sections is secure and the O ring seal is in place When replacing the flameproof cover casting ensure that it is square with t...

Page 3: ...1 Cable Glands The BExDS120D and BExDS110D sounders have dual cable gland entries which have an M20 x 1 5 entry thread as standard Only cable glands approved for Ex d applications can be used which must be suitable for the type of cable being used and also meet the requirements of the Ex d flameproof installation standard EN60079 14 2008 IEC60079 14 2007 When only one cable entry is used the other...

Page 4: ...y clockwise position 15 End of Line Monitoring DC Units On BExDS120D and BExDS110D DC units dc reverse line monitoring can be used if required All DC sounders have a blocking diode fitted in their supply input lines An end of line monitoring diode or an end of line monitoring resistor can be connected across the ve and ve terminals If an end of line resistor is used it must have a minimum resistan...

Page 5: ...ry and Temperature Classification The units can be installed in locations with the following conditions Area Classification Gas Zone 1 Explosive gas air mixture likely to occur in normal operation Zone 2 Explosive gas air mixture not likely to occur and if it does it will only exist for a short time Gas Groupings Group IIA Propane Group IIB Ethylene Group IIC 55ºC Hydrogen and Acetylene Temperatur...

Page 6: ...exceed 70ºC and therefore suitable heat resisting cable glands must be used with a rated service temperature of at least 110ºC 12 Cable Connections See drawing C and D 13 Tone Selection and 2nd and 3rd Stage Alarms See wiring diagram E 14 Volume Control See drawing F 15 End of Line Monitoring DC Units On BExDS120D and BExDS110D DC units dc reverse line monitoring can be used if required All DC sou...

Page 7: ... om vast te zetten Serrer la vis pour une fixation sûre Zum Sichern Schraube anziehen Stringere la vite per il fissaggio Stram skruen for å feste Aperte o parafuso para fixar Apriete el tornillo para asegurar Dra åt skruven för att fästa Loosen screw to adjust Løsn skruen for at tilpasse Schroef losdraaien om af te stellen Desserrer la vis pour régler Zum Regulieren Schraube lockern Allentare la v...

Page 8: ...Acton London W3 7QH sales e 2 s com Tel 44 0 208 743 8880 www e 2 s com Fax 44 0 208 740 4200 Document No BExDS120D and BExDS110D Gas Dust English Issue E Four Sheets 19 02 10 8 Wiring Diagram E S3 S2 BExS120D and BExS110D DC Units S2 S3 S2 S3 S2 S3 C S3 S2 L N E BExS120D and BExS110D AC Units C S2 S3 N C S2 S3 N C S2 S3 E E L L E N L Drawing F BExS110D BExS120D S2 S3 C C S3 S2 N L ...

Page 9: ... områder med følgende forhold Klassificeringsareal for gasser Zone 1 Eksplosiv gas og luftblanding kan forekomme ved normal drift Zone 2 Eksplosiv gas og luftblanding forekommer sandsynligvis ikke og hvis det sker vil det kun være for en kort tidsperiode Gasgrupperinger Gruppe IIA Propan Gruppe IIB Ethylen Gruppe IIC 55ºC Hydrogen og acetylen Temperaturklassifikation T1 400o C T2 300o C T3 200o C ...

Page 10: ...el arbejdstemperatur på mindst 110ºC 12 Kabelforbindelser Se illustrationen C og D 13 Tonevalg og 2 og 3 niveau alarmer Se ledningsdiagram E 14 Volumenkontrol Se illustration F 15 Linieslutovervågning DC enheder På BExDS120D og BExDS110D DC enheder kan der anvendes returlinieovervågning efter behov Alle DC soundere har en spærrediode i strømindgangsledningerne En diode til linieslutovervågning ell...

Page 11: ... De eenheden kunnen worden geïnstalleerd op plaatsen waar de volgende omstandigheden heersen Zoneclassificatie gas Zone 1 Ontplofbaar gas luchtmengsel is waarschijnlijk bij normaal bedrijf Zone 2 Ontplofbaar gas luchtmengsel is onwaarschijnlijk en indien dit ontstaat zal het waarschijnlijk slechts korte tijd aanwezig blijven Gasgroeperingen Groep IIA Propaan Groep IIB Ethyleen Groep IIC 55ºC Water...

Page 12: ...r bij de kabelingang hoger zijn dan 70ºC en moeten dus geschikte hittebestendige kabelwartels worden gebruikt met een nominale werktemperatuur van ten minste 110º C 12 Kabelaansluitingen Zie tekening C en D 13 Toonkeuze en alarmen in 2e en 3e fase Zie bedradingsschema E 14 Volumeregeling Zie tekening F 15 Bewaking aan einde van lijn DC eenheden Op BExDS120D en BExDS110D DC eenheden kan desgewenst ...

Page 13: ...ément aux codes de pratique locaux 5 Classification des zones du groupe et de la catégorie de gaz et des températures Les unités peuvent être installées dans des endroits respectant les conditions suivantes Classification de zone gaz Zone 1 Mélange d air et de gaz explosif pouvant survenir en condition normale Zone 2 Mélange d air et de gaz explosif ne pouvant pas survenir et qui dans le cas contr...

Page 14: ...s températures ambiantes élevées c est à dire supérieures à 40ºC la température d entrée du câble peut excéder 70ºC et des câbles résistants à la chaleur doivent être utilisés d une température de service assignée de 110ºC minimum 12 Connexions de câble Se reporter au schéma C et D 13 Sélection du timbre et alarmes de 2ème et 3ème étape Se reporter au schéma de câblage E 14 Contrôle du volume Se r...

Page 15: ...e können an Standorten aufgestellt werden an denen die folgenden Bedingungen vorliegen Bereichseinteilung Gas Zone 1 Bei normalem Betrieb kann mit hoher Wahrscheinlichkeit eine explosive Gas Luft Mischung vorliegen Zone 2 Explosive Gas Luft Mischung unwahrschein lich und sollte sie doch auftreten dann nur kurzfristig Gasgruppen Gruppe IIA Propan Gruppe IIB Äthylen Gruppe IIC 55ºC Wasserstoff und A...

Page 16: ... 110ºC zu verwenden 12 Kabelanschlüsse Siehe Zeichnung Cund D 13 Tonwahl und Alarm der 2 und 3 Stufe Siehe Schaltbild E 14 Lautstärkeregulierung Siehe Zeichnung F 15 Überwachung des Leitungsendes Gleichstromgeräte Bei BExS120D und BExS110D Gleichstromgeräten kann bei Bedarf eine Wechselstrom Sperrleitungskontrolle eingesetzt werden Alle Gleichstrom Sounder sind mit einer Sperrdiode versehen die in...

Page 17: ...ne delle zone dei gruppi di gas delle categorie e delle temperature Le unità possono essere installate in ambienti che presentano le seguenti condizioni Classificazione area Gas Zona 1 È probabile la presenza di gas esplosivo durante il normale funzionamento Zona 2 Non è probabile che sia presente gas esplosivo e se esso dovesse essere presente potrà esserlo solo per un breve periodo di tempo Grup...

Page 18: ...ri a 40 C la temperatura in ingresso dei cavi può superare 70 C per cui occorre utilizzare premistoppa adeguati resistenti al calore con una temperatura nominale di esercizio di almeno 110 C 12 Connessioni dei cavi Vedere figura C e D 13 Scelta del tono e allarmi di secondo e terzo livello Vedere lo schema dei collegamenti elettrici E 14 Controllo del volume Vedere figura F 15 Sistema di controllo...

Page 19: ...eldende lokale bransjestandarder må overholdes 5 Soner gassgruppe kategori og temperatur klassifisering Enhetene kan installeres på steder med følgende forhold Soneklassifisering gass Sone 1 Eksplosiv gass luft blanding som sannsynligvis forekommer ved normal drift Sone 2 Eksplosiv gass luft blanding som ikke vanligvis vil forekomme og om den gjør det kun vil forekomme i kort tid Gassgrupperinger ...

Page 20: ...ige kabelmuffer benyttes med godkjent driftstemperatur på minst 95 ºC 13 Kabelforbindelser Se tegningen C og D 14 Tonevalg og 2 og 3 trinnsalarmer Se kablingsskjemaet E 15 Volumkontroll Se tegningen F 16 Slutt på linje overvåking DC enheter På BExDS120D og BExDS110D DC enheter kan likestrømsreversert linjeovervåking benyttes om nødvendig Alle DC alarmer har en blokkeringsdiode montert i inngangsli...

Page 21: ... de gases categoria e temperatura As unidades podem ser instaladas em locais com as seguintes condições Classificação da Área Gás Zona 1 Probabilidade de ocorrência de mistura gasosa explosiva em funcionamento normal Zona 2 Improbabilidade de ocorrência de mistura gasosa explosiva mesmo que tal ocorra só será por período curto Grupos de gases Grupo IIA Propano Grupo IIB Etileno Grupo IIC 55ºC Hidr...

Page 22: ...de entrada do cabo pode exceder os 70º C e por isso devem usar se tubos resistentes ao calor com uma capacidade de temperatura de serviço nunca inferior a 110º C 13 Ligações do cabo Consulte o desenho C e D 14 Selecção de tom e alarmes de 2ª e 3ª fases Consulte o diagrama de ligações E 15 Controlo do volume Consulte o desenho F 16 Monitorização de fim de linha Unidades CC Nas unidades CC BExDS120D...

Page 23: ...ción de zonas grupo de gas categoría y temperatura Las unidades pueden instalarse en ubicaciones que cumplan las siguientes condiciones Gas de clasificación por área Zona 1 Mezcla explosiva de aire y gas que es posible ocurra durante el funcionamiento normal Zona 2 Mezcla explosiva improbable de aire y gas que de producirse lo hará sólo por breve tiempo Grupos de gas Grupo IIA Propano Grupo IIB Et...

Page 24: ... utilizan a temperaturas ambiente altas es decir superiores a 40ºC la temperatura de entrada del cable puede superar 70ºC por lo tanto deben usarse casquillos de cable resistentes al calor adecuados con una temperatura de servicio nominal de al menos 110ºC 12 Conexiones de los cables Véase el diagrama C y D 13 Selección de tono y alarmas de 2ª y 3ª fase Véase el diagrama de cableado E 14 Control d...

Page 25: ...rig personal under tillämpande av lokala bestämmelser 5 Zoner explosionsgrupper kategori och T klasser Enheterna får installeras på platser där följande förhållanden råder Zonindelning för gas Zon 1 Explosiv gasblandning förväntas förekomma vid normal drift Zon 2 Explosiv gasblandning förväntas förekomma sällan och då endast kortvarigt Explosionsgrupper Grupp IIA Propan Grupp IIB Etylen Grupp IIC ...

Page 26: ... överskrida 70ºC vid införingsstället Därför skall lämpliga värmeresistenta kablar med en märktemperatur på minst 110ºC användas 12 Kabelanslutningar Se ritning C och D 13 Tonval och 2 och 3 lägeslarm Se kopplingsschema E 14 Volymkontroll Se ritning F 15 Ledningsövervakning DC enheter Ledningsövervakning kan vid behov användas på DC enheterna BExDS120D och BExDS110D Alla DC högtalare har en blocke...

Page 27: ...2004 Directive 89 106 EEC Construction Products Directive CPD BExS110D24DC BExS120D24DC tones 2 3 9 15 16 17 only Notified Body for EC type Examination VdS Schadensverhütung GmbH Notified Body No 0786 Amsterdamer Str 172 174 50735 Köln Germany EC type Examination Certificate 0708 CPD 20225 Standards applied EN 54 3 2001 A1 2002 Directive 2009 26 EC Marine Equipment Directive MED BExS110D24DC M onl...