Inca PVJ3 User Manual Download Page 9

 

PVJ3 

page 9 

 

 

4.5  Start Pressure Setting 

Start pressure will now be displayed.  
The Cursor will be flashing under the first digit of the START PRESSURE 
setting. Simply type in the appropriate pressure you want the Pump to restart 
at once it has gone to sleep, example 375kPa Press 3, press 7, press 5 & 
then press Return Arrow button. 
Press the RIGHT ARROW Button to move onto the next Page. 
 

4.6  Pump Stop Minimum Speed Setting 

Pump Stop Minimum Speed will now be displayed.  
The Cursor will be flashing under the first digit of the PUMP STOP MINIMUM 
SPEED setting. The pump stop minimum speed is the speed at which the 
standby pump is turned off after the duty pump has reached the pump stop 
minimum speed plus a short time delay. 

This set point is critical to be set 

correctly so as to prevent short cycling. 
 
To set the Pump stop Min Speed you must first operate 1-off pump in 
manual with a closed discharge to find out the pump speed required to 
maintain set point pressure. Add 2% to ensure the system will get to the 
setpoint. This speed value is then entered.

 Example say 67%. Press 6, 

press 7, the Return arrow button to accept.  
Press the RIGHT ARROW Button to move onto the next Page. 
 

4.7  Sleep Shutdown Time Setting 

Sleep Shutdown Time will now be displayed.  
The Cursor will be flashing under the first digit of the SLEEP SHUTDOWN 
TIME setting. Simply type in the appropriate time value in minutes & seconds 
you want the duty pump to run on for before going to sleep, example 
20seconds Press 0, press 0, press 2, press 0 & then press Return Arrow 
button. 
Press the RIGHT ARROW Button to move onto the next Page. 
 

4.8  Standby Start Time Setting 

Standby Start Time will now be displayed.  
The Cursor will be flashing under the first digit of the STANDBY START TIME 
setting. Simply type in the appropriate time value in minutes & seconds you 
want the standby pump to be delayed from starting once the Standby Start 
Speed has been reached, example 20seconds Press 0, press 0, press 2, 
press 0 & then press Return Arrow button. 
Press the RIGHT ARROW Button to move onto the next Page. 
 
 
 
 

Summary of Contents for PVJ3

Page 1: ...eb www incacontrol com au Design Manufacture of Custom built switchboards Electronic control equipment AC DC pumping controls Installation service INCA MODEL PVJ3 TRIPLEX PRESSURE SYSTEM VARIABLE SPEE...

Page 2: ...Setting low pressure shutdown 8 4 3 Setting low pressure time delay 8 4 4 Set Point Pressure Setting 8 4 5 Start pressure Setting 9 4 6 Pump Stop Minimum Speed 9 4 7 Sleep Shutdown Time Setting 9 4 8...

Page 3: ...discharge pressure transducer It also displays the pump operating condition alarm conditions User Interface Display An LCD screen displaying 2 lines of text each 16 characters long Keypad Operator ke...

Page 4: ...supplier Environmental Specification Operating Temp 10 to 50deg C Relative Humidity Do not install in areas of high humidity Locate control panel internally where possible to help reduce heat weather...

Page 5: ...trol panel 2 3 Electrical Installation Note All cable entries must enter via the bottom of the cabinet If cables are entered via the roof Inca Control Pty Ltd reserve the right to withdraw warranty be...

Page 6: ...d in this case the pump lead is supplied by the pump manufacturer The cable entering the control panel end can be glanded using standard nylon glands run directly to the VSD terminals T1 T2 T3 The cab...

Page 7: ...on the bottom of the blue buttons You can only enter a value of as many digits as is displayed on the screen Example an input that displays 3 digits can only have 3 digit entered 3 2 Power Up Display...

Page 8: ...ss the RIGHT ARROW Button to move onto the next Page 4 2 Setting Low Pressure Shutdown Low pressure will now be displayed The Cursor will be flashing under the first digit of the LOW PRESSURE setting...

Page 9: ...ed required to maintain set point pressure Add 2 to ensure the system will get to the setpoint This speed value is then entered Example say 67 Press 6 press 7 the Return arrow button to accept Press t...

Page 10: ...g under the first digit of the 2nd STANDBY STOP TIME setting Simply type in the appropriate time value in minutes seconds you want the 2nd standby pump to be delayed from stopping once the Standby Sto...

Page 11: ...parameters to suit the live input from the field pressure transducer It is critical that the following is observed 1 Make shore pump is running at set point pressure is not wanting to call other pump...

Page 12: ...ration until the wake up pressure is again reached The pressure will fall to the wake up pressure set point where the duty pump will then start the cycle once again Each time the system goes to sleep...

Page 13: ...he switch is selected by operating the appropriate selector on the Panel facia Manual Selecting MANUAL will turn the pump on continuously at a fixed full speed Off Selecting OFF will turn the pump off...

Page 14: ...for attention under guarantee unless otherwise agreed must be returned to the factory freight paid and if accepted for free repair will be returned to the customers address in Australia free of charge...

Reviews: