Inca PVJ3 User Manual Download Page 12

 

PVJ3 

page 12 

 

12 

5  Operation 

 

5.1   System Operation 

The system is designed to maintain a constant pressure in the discharge line 
of a pumping system. The duty pump will start & ramp up & down in speed 
maintaining the set point pressure until this duty pump reaches & maintains 
100% speed for a short time delay. At this point the standby pump will start. 
Both pumps will then ramp up & down maintaining the set point pressure until 
the pumps reach & maintains (Standby stop speed) for a short time delay. At 
this point the standby pump will be turned off & the duty pump will take over 
by itself. 
The duty pump will then ramp up & down to maintain the set point pressure 
until this pump reaches & maintains the pump stop criteria plus a delay set in 
(pump shutdown delay) & will then turn off stopping all pump operation until 
the wake-up pressure is again reached.  
The pressure will fall to the wake-up pressure set point where the duty pump 
will then start the cycle once again. 
Each time the system goes to sleep the duty pump will be alternated to the 
next pump ready for the next operation. 
If a motor fails the standby pump will be started & will remain as duty until the 
faulted pump is put back on line. 
 
Pump Stop Criteria 
 

Duty Pump 

– The duty pump requires 3 things to shut down- 

 
1.  The system pressure has reached & maintains set point pressure less 

5kPa. 

2.  The motor speed is less & maintains less than the speed set in PUMP 

STOP MINIMUM SPEED. 

3.  And the time value entered into LOW STOP TIMER parameter has timed 

out.  
 

Standby Pump 

– The standby pump requires 3 things to shut down- 

 
1.  The system pressure has reached & maintains set point pressure less 

5kPa. 

2.  The motor speed is less & maintains less than the speed set in PUMP 

STOP MINIMUM SPEED.  

3.  And the time value entered into parameter STANDBY STOP TIMER. 
 
 
 
 
 

Summary of Contents for PVJ3

Page 1: ...eb www incacontrol com au Design Manufacture of Custom built switchboards Electronic control equipment AC DC pumping controls Installation service INCA MODEL PVJ3 TRIPLEX PRESSURE SYSTEM VARIABLE SPEE...

Page 2: ...Setting low pressure shutdown 8 4 3 Setting low pressure time delay 8 4 4 Set Point Pressure Setting 8 4 5 Start pressure Setting 9 4 6 Pump Stop Minimum Speed 9 4 7 Sleep Shutdown Time Setting 9 4 8...

Page 3: ...discharge pressure transducer It also displays the pump operating condition alarm conditions User Interface Display An LCD screen displaying 2 lines of text each 16 characters long Keypad Operator ke...

Page 4: ...supplier Environmental Specification Operating Temp 10 to 50deg C Relative Humidity Do not install in areas of high humidity Locate control panel internally where possible to help reduce heat weather...

Page 5: ...trol panel 2 3 Electrical Installation Note All cable entries must enter via the bottom of the cabinet If cables are entered via the roof Inca Control Pty Ltd reserve the right to withdraw warranty be...

Page 6: ...d in this case the pump lead is supplied by the pump manufacturer The cable entering the control panel end can be glanded using standard nylon glands run directly to the VSD terminals T1 T2 T3 The cab...

Page 7: ...on the bottom of the blue buttons You can only enter a value of as many digits as is displayed on the screen Example an input that displays 3 digits can only have 3 digit entered 3 2 Power Up Display...

Page 8: ...ss the RIGHT ARROW Button to move onto the next Page 4 2 Setting Low Pressure Shutdown Low pressure will now be displayed The Cursor will be flashing under the first digit of the LOW PRESSURE setting...

Page 9: ...ed required to maintain set point pressure Add 2 to ensure the system will get to the setpoint This speed value is then entered Example say 67 Press 6 press 7 the Return arrow button to accept Press t...

Page 10: ...g under the first digit of the 2nd STANDBY STOP TIME setting Simply type in the appropriate time value in minutes seconds you want the 2nd standby pump to be delayed from stopping once the Standby Sto...

Page 11: ...parameters to suit the live input from the field pressure transducer It is critical that the following is observed 1 Make shore pump is running at set point pressure is not wanting to call other pump...

Page 12: ...ration until the wake up pressure is again reached The pressure will fall to the wake up pressure set point where the duty pump will then start the cycle once again Each time the system goes to sleep...

Page 13: ...he switch is selected by operating the appropriate selector on the Panel facia Manual Selecting MANUAL will turn the pump on continuously at a fixed full speed Off Selecting OFF will turn the pump off...

Page 14: ...for attention under guarantee unless otherwise agreed must be returned to the factory freight paid and if accepted for free repair will be returned to the customers address in Australia free of charge...

Reviews: