Inca PVJ3 User Manual Download Page 5

 

PVJ3 

page 5 

 

 

2.0  Installation 

 

Note: If any damage to control panel if found, please notify Inca Control 
Pty Ltd as soon as possible prior to installation. 

The control panel can be wall mounted separately from the pumping unit; 
distance is governed by the cable sizing to the motor.  
It is recommended that the control panel is within view of the pumping unit for 
safety reasons. If not in view lockable isolating switches must be installed at 
the pump motors. 

  

 

2.1  Mechanical Installation 

Mount the control panel via the mounting holes in each corner at the back of 
the enclosure using minimum 6mm screws, nuts & locking washers, or 
masonry anchors. 
Install in a dry well ventilated location that matches with environmental 
specification in 1.2 above. 

 
2.2  Sensor Installation 

Locate the pressure transducer in the discharge pipe work as close as 
practical to the control panel. 
  

2.3  Electrical Installation 
Note: All cable entries must enter via the bottom of the cabinet. If cables 
are entered via the roof Inca Control Pty Ltd reserve the right to 
withdraw warranty because of the possibility of shaving entering 
sensitive electronic equipment. 

 

Transducer wiring

 

The pressure transducer must be wired in 1 pair overall screened data cable. 
This type of cable provides the most protection against electrical noise & 
allows a more accurate outcome. 
Connect to the sensor as per data supplied by the sensor supplier 
At the control panel connect the positive lead to terminal No10 & the return 
signal to terminal No12. 
The screen must be solidly earthed, with a saddle clamp providing the best 
screening earth. 
 

Float switch wiring

 

The float switch is wired in the cable supplied with switch. The cable to be 
connected must close the circuit when water in the suction tank falls 
Connect the float switch as per data supplied by the float switch supplier 
At the control panel connect the float switch lead to terminal No10 & terminal 
No11. 
 

Summary of Contents for PVJ3

Page 1: ...eb www incacontrol com au Design Manufacture of Custom built switchboards Electronic control equipment AC DC pumping controls Installation service INCA MODEL PVJ3 TRIPLEX PRESSURE SYSTEM VARIABLE SPEE...

Page 2: ...Setting low pressure shutdown 8 4 3 Setting low pressure time delay 8 4 4 Set Point Pressure Setting 8 4 5 Start pressure Setting 9 4 6 Pump Stop Minimum Speed 9 4 7 Sleep Shutdown Time Setting 9 4 8...

Page 3: ...discharge pressure transducer It also displays the pump operating condition alarm conditions User Interface Display An LCD screen displaying 2 lines of text each 16 characters long Keypad Operator ke...

Page 4: ...supplier Environmental Specification Operating Temp 10 to 50deg C Relative Humidity Do not install in areas of high humidity Locate control panel internally where possible to help reduce heat weather...

Page 5: ...trol panel 2 3 Electrical Installation Note All cable entries must enter via the bottom of the cabinet If cables are entered via the roof Inca Control Pty Ltd reserve the right to withdraw warranty be...

Page 6: ...d in this case the pump lead is supplied by the pump manufacturer The cable entering the control panel end can be glanded using standard nylon glands run directly to the VSD terminals T1 T2 T3 The cab...

Page 7: ...on the bottom of the blue buttons You can only enter a value of as many digits as is displayed on the screen Example an input that displays 3 digits can only have 3 digit entered 3 2 Power Up Display...

Page 8: ...ss the RIGHT ARROW Button to move onto the next Page 4 2 Setting Low Pressure Shutdown Low pressure will now be displayed The Cursor will be flashing under the first digit of the LOW PRESSURE setting...

Page 9: ...ed required to maintain set point pressure Add 2 to ensure the system will get to the setpoint This speed value is then entered Example say 67 Press 6 press 7 the Return arrow button to accept Press t...

Page 10: ...g under the first digit of the 2nd STANDBY STOP TIME setting Simply type in the appropriate time value in minutes seconds you want the 2nd standby pump to be delayed from stopping once the Standby Sto...

Page 11: ...parameters to suit the live input from the field pressure transducer It is critical that the following is observed 1 Make shore pump is running at set point pressure is not wanting to call other pump...

Page 12: ...ration until the wake up pressure is again reached The pressure will fall to the wake up pressure set point where the duty pump will then start the cycle once again Each time the system goes to sleep...

Page 13: ...he switch is selected by operating the appropriate selector on the Panel facia Manual Selecting MANUAL will turn the pump on continuously at a fixed full speed Off Selecting OFF will turn the pump off...

Page 14: ...for attention under guarantee unless otherwise agreed must be returned to the factory freight paid and if accepted for free repair will be returned to the customers address in Australia free of charge...

Reviews: