1.4 IDA In-Line Deflagration Arrester Certification
The IDA certification is optional. Contact Imperial
Systems to verify if your CMAXX is equipped with the
IDA certification.
The CMAXX using the Proprietary DELTAMAXX IDA
Filters is proven to completely isolate flame transmission
and stop combustion from passing through the filters.
With IDA you can safely return air back into the workplace.
This flame and deflagration isolation meets at least
one of the required methods required by NFPA. Third
party test results are available upon request.
To maintain IDA certification on collector, you must:
• Provide a dust sample for KST testing or provide a
copy of a completed KST test.
• Dust cannot exceed a rating of 200 KST.
• Use Certified DELTAMAX IDA Filters.
• Differential pressure cannot exceed 5 Inches of
Water Column.
• Install a broken bag detector in return air duct.
• Install a burst indicator on pressure relief panel.
• Ground the Dust Collector
In the event of a deflagration the following must be
performed before the unit is returned to service.
1. Inspect unit for any deformation, or stress cracks.
2. Inspect tube sheet to verify there is no deforming,
and filters will seal against it properly.
3. Inspect door hardware for proper function, verify
there is no deformation or stress cracks in latch mechanism.
4. Inspect lift rails for proper function.
5. Replace filters with Certified DELTAMAXX IDA
Filters. Filters can only be purchased from Imperial
Systems.
6. Replace pressure relief panel and burst indicator.
7. Replace door gasket.
8. Replace explosion vent braces.
Imperial Systems does offer an inspection service to
verify your collector is operational. Please contact your
sales representative for current pricing.
1.5 Fire Protection And Safety Equipment
The customer assumes the responsibility to contact
their insurance company and or AHJ (Authority having
Jurisdiction) to see what is required to meet the needs
of fire protection, explosion ventilation, deflagration,
isolation and any other related equipment.
It is the customer’s responsibilities to relay this
information to Imperial Systems so that we can properly
select and size the necessary equipment to meet their
requirements.
The customer should adhere to any and all NFPA,
OSHA, federal, state, codes, rules, and regulations.
imperialsystemsinc.com
6
Imperial
Systems
Inc.
WARNING
Prevent serious injury or death.
Not following above requirements will void
IDA rating and could result in property
damage, death, or serious injury.
Summary of Contents for CMAXX
Page 9: ...imperialsystemsinc com 9 Imperial Systems Inc 3 Safety Labels...
Page 24: ...imperialsystemsinc com 24 Imperial Systems Inc 11 ELECTRICAL 11 1 SOLENOID SCHEMATIC...
Page 25: ...imperialsystemsinc com 25 Imperial Systems Inc 11 2 DCT1000 SCHEMATIC...
Page 26: ...imperialsystemsinc com 26 Imperial Systems Inc 11 3 SOLENOID HEATER SCHEMATIC OPTIONAL...
Page 27: ...imperialsystemsinc com 27 Imperial Systems Inc 11 4 INTEGRATED CONTROLS WIRING DIAGRAM...
Page 28: ...MADE IN THE USA 8 0 0 9 1 8 3 0 1 3 i m p e r i a l s y s t e m s i n c c o m...