ERROR 37
Low power supply voltage
The boiler power supply voltage exceeds 190 VDC.
No
Restore the correct electric power of the appliance (230 VDC ±10%).
Yes
The electric power supply connection wires and relative external fuses
are integral.
No
Restore the electric connection/replace the cables/external fuses.
Yes
Replace the P.C.B.
ERROR 38
Loss of flame signal
It is displayed every time the board, with burner on, looses the flame signal.
If normal conditions are restored, the boiler re-starts correct functioning without having to be reset.
If the error persists, after several ignition attempts, the error 38 switches to error "01" or error "02".