Fig. 3-1

3

  BOILER COMMISSIONING 

(INITIAL CHECK)

To commission the boiler:

- ensure that the declaration of conformity of 

installation is supplied with the appliance;

- ensure that the type of gas used corresponds to 

boiler settings;

- check  connection  to  a  230V-50Hz  power 

mains, correct L-N polarity and the earthing 

connection;

- make sure the heating system is filled with 

water  and  that  the  manometer  indicates  a 

pressure of 1÷1.2 bar;

- switch the boiler on and ensure correct ignition;

- check the ∆p gas values in domestic hot water 

and heating modes;

- check the CO

2

 in the combustion products at 

maximum and minimum flow rate;

- check activation of the safety device in the event 

of no gas, as well as the relative activation time;

- check activation of the main switch located 

upstream from the boiler and in the boiler;

- check that the intake and/or exhaust terminals 

are not blocked;

- ensure activation of all adjustment devices;
- seal the gas flow rate regulation devices (if 

settings are modified);

- ensure production of domestic hot water;

- ensure sealing efficiency of water circuits;
- check  ventilation  and/or  aeration  of  the 

installation room where provided.

If even only a single safety check offers a negative 

result, do not commission the system.

3.1  HYDRAULIC DIAGRAM.

Key:

  1  -  Condensate drain trap

  2  -  Water inlet filter*

  3  -  Domestic hot water flow meter

  4  -  Domestic hot water flow rate adjuster

  5  -  Domestic hot water probe

  6  -  Gas valve

  7  -  Gas valve outlet pressure point (P3)

  8  -  Aqua Celeris Resistance

  9  -  Aqua Celeris

  10  -  Venturi positive sign (P1)

  11  -  Venturi negative sign (P2)

  12  -  Air/gas Venturi manifold

  13  -  Fan

  14  -  Gas nozzle

  15  -  Detection electrode

  16  -  Air intake pipe

  17  -  Condensation module

  18  -  Manual vent valve

  19  -  Flue probe

  20  -  Air sample point 

  21  -  ∆p gas pressure point

  22  -  Flue sample point

  23  -  Flue hood

  24  -  Heat exchanger safety thermofuse

  25  -  Flow probe

  26  -  Safety thermostat

  27  -  Ignition electrodes

  28  -  Burner

  29  -  Condensation module cover

  30  -  Return probe

  31  -  System expansion vessel

  32  -  Air vent valve 

  33  -  Boiler pump

  34  -  System draining valve

  35  -  System pressure switch

  36  -  3-way valve (motorised)

  37  -  DHW heat exchanger

  38  -  Adjustable by-pass

  39  -  3 bar safety valve

  40  -  System filling valve

  41  -  DHW inlet probe

* =

 Attention:

 check the presence and cleanliness 

of the water inlet filter, which guarantees 

the efficiency of the boiler

  G  -  Gas supply

  SC  -  Condensate drain

 AC  -  Domestic hot water outlet

  AF  -  Domestic hot water inlet

  R  -  System return

  M  -  System flow

Summary of Contents for VICTRIX Superior TOP 32 E

Page 1: ...VICTRIX Superior TOP 32 E IE Instruction and warning book 1 032471IE...

Page 2: ...DECLARES THAT the Immergas boiler model Victrix Superior TOP 32 E is in compliance with the same European Community Directives Mauro Guareschi Research Development Director Signature Dear Client Our c...

Page 3: ...r any damage caused to the household appliances It is also advisable to not position furnishings furniture etc under the boiler for the above mentioned reasons In the event of malfunctions faults or i...

Page 4: ...The instructions of the manufacturer of this liquid must be followed scrupulously regarding the percentage necessary with respect to the minimum temperature at which the system must be kept An aqueous...

Page 5: ...lime scale apparatus is preserved for example limescale deposits from the slurry formation and other noxious deposits Waterconnectionsmustbemadeinarationalway using the couplings on the boiler templa...

Page 6: ...the Super CAR must be used with its climate thermostat function disabled i e it must be set to On Off mode CARV2 Super CAR or On Off chrono thermostat electrical connection Optional The operations des...

Page 7: ...This information allows calculations to be made to verify the possibility of setting up various flue configurations Positioning of the gaskets black for green range flue extraction systems Position t...

Page 8: ...Intake and Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust...

Page 9: ...laps Fit the male side smooth of the exhaust terminal into the the female side of the bend 90 80 making sure that the relevant wall sealing plate is already fitted this will ensure the hold and joinin...

Page 10: ...ested Horizontal intake exhaust kit 80 125 Kit assembly Fig 1 15 for the installation of kit 80 125 the flanged adapter kit must be used to be able to install the flue system 80 125 Install the flange...

Page 11: ...take exhaust pipe 5 Fit the 60 100 3 concentric terminal pipe with the male end 5 smooth into the flange 2 up to the stop making sure that the wall sealing plate has been fitted 3 this will ensure sea...

Page 12: ...flat flange present in the lateral hole with respect to the central one according to needs and replace it with the flange 3 positioning the gasket 2 already present in the boiler and tighten using th...

Page 13: ...he removal of possible condensate forming in the exhaust pipe tilt the pipes towards the boiler with a min slope of 1 5 Assemble the lid A complete with adapter 1 and wall plugs 6 and assemble the flu...

Page 14: ...ue technical slot The max possible length of the 60 flexible ducting vertical section is equal to 30 m This length is obtained considering the complete 80 exhaust terminal 1m of 80 pipe in exhaust two...

Page 15: ...ent the circulation pump by loosening the front cap and keeping the motor running Re tighten the cap after the operation 1 19 FILLING THE CONDENSATE TRAP On first lighting of the boiler combustion pro...

Page 16: ...the power supplied by the burner greater the power greater the speed Moreover inside the parameter it is possible to regulate the operation range of the pump by setting the maximum speed adjustable fr...

Page 17: ...ly This kit is very useful for maintenance because it allows to empty just the boiler without having to empty the entire system Moreover the version with filter preserves the functioning characteristi...

Page 18: ...e of electrical power requires some fundamental rules to be observed do not touch the appliance with wet or moist parts of the body do not touch when barefoot never pull electrical cables or leave the...

Page 19: ...tral heating in order to evacuate residual flue gases F5 Postcirculation in progress Pump in function after a request for domestic hot water or central heating in order to cool the primary circuit P33...

Page 20: ...By turning the selector switch 1 in a clockwise direction the temperature increases and in an anti clockwise direction it decreases During the heating of the domestic hot water DHW ON appears on the...

Page 21: ...chnician must be called e g Immergas After Sales Service Maximum No of resets Available number of resets already made Insufficient system pressure Water pressure inside the central heating system that...

Page 22: ...in the case of malfunctioning or anomaly the display of the temperature is replaced by the relative error code present in the table Par 2 6 2 7 BOILER SHUTDOWN Switchtheboileroffbypressingthe button d...

Page 23: ...The display is always lit up OFF The display only lights up when the controls are accessed and remains on for 5 seconds after the last operation performed P32 D C P32 B D C ITALIANO D x select C All d...

Page 24: ...t by the external probe See OFFSET on the external probe graphics Fig 1 8 by modifying the temperature from 15 C to 15 C P94 D x select C It defines the flow temperature of the zone number 3 at low te...

Page 25: ...or aeration of the installation room where provided If even only a single safety check offers a negative result do not commission the system 3 1 HYDRAULIC DIAGRAM Key 1 Condensate drain trap 2 Water i...

Page 26: ...the system pressure is within established limits Check that the radiator valves are not closed and also the functionality of the pump Siphon blocked This may be caused by dirt or combustion products...

Page 27: ...board air gas circuit components or in the case of installations with fume extraction systems with horizontal concentric pipe measuring more than 1 metre The boiler heat output is correlated to the le...

Page 28: ...ive take the heating selector switch to maximum turn it in a clockwise direction until 99 is seen on the display To have an exact value of CO2 in the flue gases the technician must insert the sampling...

Page 29: ...the maximum delivery temperature With the external probe present it defines the maximum flow temperature corresponding to functioning with minimum external temperature see graphics Fig 1 8 can be set...

Page 30: ...juster on the various levels Auto automatic functioning therefore with variable flow rate Open adjuster completely open therefore maximum flow rate available 08 L M 10 L M and 12 L M ffunctioning with...

Page 31: ...t upstream from the boiler Set the P 71 function on P 71 1 Par 3 8 When the boiler inlet water is at a temperature that is equal or greater with respect to that set by the domestic hot water selector...

Page 32: ...with that indicated by the regulations in force 3 17 CASING REMOVAL To facilitate boiler maintenance the casing can be completely removed as follows disassemble the front 1 of the boiler by loosening...

Page 33: ...kg h mbar mm H2 O kg h mbar mm H2 O 32 0 27520 3 45 8 30 84 6 2 58 8 40 85 7 2 53 8 20 83 6 31 0 26660 3 34 7 80 79 6 2 49 7 88 80 4 2 45 7 76 79 2 30 0 25800 3 23 7 33 74 7 2 41 7 39 75 3 2 37 7 34...

Page 34: ...ith burner On Off 80 60 C 0 48 0 30 Heat loss at flue with burner On Off 80 60 C 0 03 2 20 Central heating circuit max operating pressure bar 3 Central heating circuit max operating temperature C 90 A...

Page 35: ......

Page 36: ...immergas com Immergas S p A 42041 Brescello RE Italy T 39 0522 689011 F 39 0522 680617 This instruction booklet is made of ecological paper Code 1 032471IE rev 15 036945 001 09 2012...

Reviews: