26
STESkW ed 05/06
EOLO Star 23 kW
Technical Documentation
Technical Documentation
- press the d.h.w. temperature setting push buttons (3) + and
(4) - simultaneously to cancel the operation;
Note:
if no push buttons are pressed for 30 seconds the
operation is cancelled automatically.
Solar panel selection.
This function is useful for setting the
boiler so that it can work with solar panels.
By setting parameter P0 to
on
“solare” mode, the burner
shut-down is related to the domestic hot water temperature
regulation. In
oF
mode, the burner shut-down occurs at
maximum value.
N.B.:
in combination with a solar valve kit, it is preferable to
set the parameter P0 to
on
“solare” mode.
Solar panel selection
Range of settable values
Parameter
on
“solare” -
oF
(Standard setting)
P0
Selecting the type of gas.
Setting this function is used to adjust
the boiler so it can work with LPG or natural gas.
Selecting the type of gas
Range of settable values
Parameter
LG
(LPG) or
nG
(Natural Gas)
(Standard setting)
P1
Gas G110 - China gas.
Setting this function is used to adjust
the boiler so it can work with the first family gases.
Gas G110 - China Gas (first family gas)
Range of settable values
Parameter
on - oF
(Standard setting)
P2
Anti-leak function.
This function reduces central heating
temperature to 57°C if a d.h.w. circulation is found in the
central heating mode.
Activating the anti-leak function
Range of settable values
Parameter
on
(Standard setting)
- oF
P3
Post d.h.w. circulation function.
With the post circulation
function active after domestic hot water has been drawn, the
pump is kept working for 2.5 seconds in the Winter phase
and 1.5 seconds in the Summer phase to reduce the formation
of scale.
Activating post d.h.w. circulation
Range of settable values
Parameter
on
(Standard setting)
- oF
P4
Central heating power.
The EOLO Star 23 kW boiler featu-
res electronic modulation that adapts boiler power to the real
heat requirements of the home. So the boiler works normally
in a variable range of gas pressures going from the minimum
to maximum central heating power according to the system’s
thermal load.
Note:
the EOLO Star 23 kW boiler is made and calibrated at
the nominal output in the central heating phase. But you need
about 10 minutes for it to reach the nominal heating output,
modifiable by selecting parameter (P6).
Note:
if the “Minimum central heating power” and “Maxi-
mum central heating power” parameters are selected when
there is a central heating request, boiler ignition is allowed
and powering of the modulation coil with a current equal to
the relative value set.
Minimum central heating power
Range of settable values
Parameter
from
0
% Imax. a
63
% Imax
(factory
set at 9.3 kW equivalent to 8,000 kcal/h)
P5
Maximum central heating power
Range of settable values
Parameter
from
0
% Imax. to
99
% Imax.
(Standard setting)
P6
Timer settings.
The boiler has an electronic timer that prevents
frequent burner ignitions in the central heating mode.
The boiler has its own standard timer set at 3 minutes.
Central heating ignitions timer
Range of settable values
Parameter
from
1
to
10
3 = 3 minutes
(Standard setting)
1 = 30 seconds
P7
Central heating ramp timer.
The boiler carries out a 10 mi-
nute ignition ramp to go from minimum power to maximum
central heating power.
Central heating ramp timer
Range of settable values
Parameter
from
1
a
10
10 = 10 minutes
(Standard setting)
1 = 30 seconds
P8