Flue gas separator adjustment.
For correct
functioning of the boiler it is necessary to regu-
late the flue gas shutter positioned on the air/flue
gas sample points (Fig. 1-11).
Adjustment is carried out by loosening the
front retainer screw and moving the indicator
to the correct position, aligning its value to the
horizontal reference. Once adjustment has been
performed, tighten the screw to fix the separator.
The appropriate adjustment is chosen based on
type of pipe and its extension: this calculation
can be made using specific tables.
Intake diaphragm installation.
For correct
boiler functioning with Ø 80 separator kits and
drain measuring > 1 m a diaphragm must be
installed on the sealed chamber intake hole and
before the intake pipe (Fig. 1-12). The appropriate
diaphragm is chosen based on type of pipe and
its maximum extension: this calculation can be
made using the tables below:
N.B.:
the diaphragms are supplied together with
the boiler as standard.
DIAPHRAGM
Shutter regulation table.
Flue gas shutter notch
Type of installation
(duct length in metres)
2
4
7
10
Ø 60/100 horizontal concentric kit
-
From 0 to
0.5
From 0.5 to
1.5
From 1.5 to
3.0
Ø 60/100 vertical concentric kit
-
From 0 to
2.2
From 2.2 to
3.7
From 3.7 to
4.7
Ø 80/125 horizontal concentric kit
-
From 0 to
0.5
From 0.5 to
4.6
From 4.6 to
7.4
Ø 80/125 vertical concentric kit
From 0 to
5.4
From 5.4 to
9.5
From 9.5 to
12.2
Ø 80 vertical separator kit without bends
*From 0
to 20
*From 20
to 40
**From 0
to 22
**From 22
to 32
Ø 80 horizontal separator kit with two bend
*From 0
to 16
*From 16
to 35
**From 0
to 17
**From 17
to 28
Direct intake kit and Ø 80 drain in B
22
configuration
From 0 to 1
-
From 1 to 12
-
*
These maximum extension values are considered intake with 1 metre exhaust pipe.
**
These maximum extension values are considered in draining with 1 metre intake pipe and Ø 50 diaphragm on the intake hole.
The cover kit includes:
N° 1 Thermoformed cover
N° 1 Gasket locking plate
N° 1 Gasket
N° 1 Gasket tightening clip
N° 1 Intake hole covering plate
The terminal kit includes:
N° 1 Gasket
N° 1 Discharge flange Ø 80
N° 1 Bend 90° Ø 80
N° 1 Drain pipe Ø 80
N° 1 Wall sealing plate