1.7  REMOTE CONTROLS AND 

ROOM CHRONO-THERMOSTATS 

(OPTIONAL).

The boiler is prepared for the application of room 

chrono-thermostats or remote controls, which 

are available as optional kits.

All Immergas chrono-thermostats are connected 

with 2 wires only. Carefully read the user and 

assembly instructions contained in the acces-

sory kit.
• On/Off digital Immergas chrono-thermostat 

(Fig. 1-4). The chrono-thermostat allows:

  - set two room temperature value: one for 

daytime (comfort temperature) and one for 

night-time (reduced temperature);

  - set a weekly program with four daily switch 

on and switch off times;

  -  select the required operating mode from the 

various possible alternatives:

    - manual mode (with adjustable tempera-

ture).

    - automatic mode (with set program).
    - forced automatic mode (momentarily 

changing the temperature of the automatic 

program).

  The chrono-thermostat is powered by two 1.5V 

LR 6 type alkaline batteries.

• Comando Amico Remoto remote control

V2

 

(CAR

V2

) (Fig. 1-6) with chrono-thermostat 

function. In addition to the functions described 

in the previous point, the CAR

V2

 panel enables 

the user to control all the important informa-

tion regarding operation of the appliance and 

the heating system with the opportunity to eas-

ily intervene on the previously set parameters, 

without having to go to where the appliance 

is installed. The panel is provided with self-

diagnosis to display any boiler functioning 

anomalies. The climate chrono-thermostat 

incorporated into the remote panel enables 

the system flow temperature to be adjusted to 

the actual needs of the room being heated, in 

order to obtain the desired room temperature 

with extreme precision and therefore with 

evident saving in running costs. The CAR

V2

 is 

fed directly by the boiler by means of the same 2 

wires used for the transmission of data between 

the boiler and device.

Important:

 if the system is subdivided into zones 

using the relevant kit, the CAR

V2

 must be used 

with its climate thermostat function disabled, i.e. 

it must be set to On/Off mode.

Comando Amico Remoto Remote Control 

V2

 

or On/Off chrono-thermostat electrical con-

nections (Optional)

The operations described 

below must be performed after having removed 

the voltage from the appliance.

 Any thermostat 

or On/Off environment chrono-thermostat must 

be connected to clamps 40 and 41 eliminating 

jumper X40 (Fig. 3-2). Make sure that the On/

Off thermostat contact is of the “clean” type, i.e. 

independent of the mains voltage, otherwise the 

P.C.B. would be damaged. Any Comando Amico 

Remoto Remote Control 

V2

 must be connected to 

clamps 41 and 44 eliminating jumper X40 on the 

P.C:B., paying attention not to invert the polarity 

in the connections (Fig. 3-2).

Important:

 if the Comando Amico Remoto 

Remote Control 

V2

 or any other On/Off chrono-

thermostat is used, arrange two separate lines in 

compliance with current regulations regarding 

electrical systems. No boiler pipes must ever be 

used to earth the electric system or telephone 

lines. Ensure elimination of this risk before mak-

ing the boiler electrical connections.

1.8   EXTERNAL PROBE (OPTIONAL).

The boiler is designed for the application of the 

Room Thermostat (Fig. 1-5) which is available 

as an optional kit.  Refer to the relative instruc-

tion sheet for positioning of the external probe.

The probe can be connected directly to the boiler 

electrical system and allows the max. system 

flow temperature to be automatically decreased 

when the external temperature increases, in 

order to adjust the heat supplied to the system 

according to the change in external temperature. 

The external probe always acts when connected 

independently from the presence or type of room 

thermostat used. The correlation between system 

flow temperature and outdoor temperature is de-

termined by the position of the selector switch on 

the boiler control panel according to the curves 

shown in the diagram (Fig. 1-6). The electric con-

nection of the external probe must be made on 

clamps 38 and 39 on the boiler P.C.B. (Fig. 3-2).

MAX

MIN

Position of the central heating tem-

perature user adjustment

Comando Amico Remoto remote control

V2

 (CAR

V2

) On/

Off digital chrono-thermostat.

Summary of Contents for 3.020928

Page 1: ...MAIOR EOLO X 28 Instruction and recommendation booklet 1 038769ENG...

Page 2: ......

Page 3: ...specified in the regulations in force and principles of good practice In compliance with legislation in force the systems must be designed by qualified professionals within the dimensional limits esta...

Page 4: ...ce 19 2 2 General warnings 19 2 3 Control panel 19 2 4 Using the boiler 20 2 5 Troubleshooting 21 2 6 Boiler shutdown 22 2 7 Restoring central heating system pressure 22 2 8 System draining 22 2 9 Ant...

Page 5: ...ances underneath the boiler as they could be damaged if the safety valve intervenes if the drain trap is blocked or if there are leaks from the hydraulic connec tions otherwise the manufacturer cannot...

Page 6: ...ts the central heating circuit from freez ing by introducing a top quality anti freeze liquid into this circuit which is not noxious to health The instructions of the manufacturer of this liquid must...

Page 7: ...cal standards in force in order to protect the system and the appliance from deposits e g scale slurry or other hazardous deposits Water connections must be made in a rational way using the couplings...

Page 8: ...h its climate thermostat function disabled i e it must be set to On Off mode Comando Amico Remoto Remote Control V2 or On Off chrono thermostat electrical con nections Optional The operations describe...

Page 9: ...haust in individual flue or to the outside The boiler with this type of configuration is classified as type B22 in accordance with the technical standards in force With this configuration air intake t...

Page 10: ...with the boiler as standard DIAPHRAGM Shutter regulation table Flue gas shutter notch Type of installation duct length in metres 2 4 7 10 60 100 horizontal concentric kit From 0 to 0 5 From 0 5 to 1...

Page 11: ...6 Exhaust m 2 0 Terminal complete with concentric vertical intake exhaust 80 125 Intake and Exhaust 33 m 2 0 m 5 5 Intake m 14 3 Exhaust m 11 0 Concentric vertical intake exhaust termi nal 80 125 Inta...

Page 12: ...it 80 125 Kit assembly Fig 1 18 install the bend with flange 2 onto the central hole of the boiler inserting the gasket 1 and tighten using the screws in cluded in the kit Fit the male end smooth of t...

Page 13: ...in the figure Combustion products are expelled from pipe S Air is taken in through pipe A for combustion The intake pipe A can be installed either on the right or left hand side of the central exhaust...

Page 14: ...screws included in the kit Remove the flat flange present in the lateral hole with respect to the central one ac cording to needs and replace it with the flange 3 positioning the gasket 2 already pre...

Page 15: ...gas exhaust outlets to the same height Temperature loss in insulated flue ducting To prevent problems of flue gas condensate in the insulated exhaust pipe 80 due to flue gas cooling through the wall t...

Page 16: ...edatlowspeedtoensurerelease of air bubbles in the water via the boiler and heating system vents The boiler has a built in automatic venting valve on the circulator Check if the cap is loose Open the r...

Page 17: ...n type B it is compulsory to mount the appropriate top protection cover along with the flue exhaust kit Anti freeze kit with resistance on request If the boiler is installed in a place where the tempe...

Page 18: ...itive signal pressure point 8 Negative signal pressure point 9 Flue pressure switch 10 Flow probe 11 Fumes hood 12 Safety thermostat 13 Primary heat exchanger 14 Ignition and detection electrodes 15 S...

Page 19: ...cal power requires some funda mental rules to be observed do not touch the appliance with wet or moist parts of the body do not touch when barefoot never pull electrical cables or leave the appli ance...

Page 20: ...to the boiler being powered without presence of flame Each time the burner ignites the relative flame present symbol is displayed 11 with relative output scale Operation with Comando Amico RemotoV2 C...

Page 21: ...nables fan start up incorrectly or in the event of a flue gas pressure switch fault If normal conditions are restored the boiler restarts without having to be reset 1 12 Storage tank probe anomaly If...

Page 22: ...y of the appliance and the domestic hot water heating system in areas where the temperature falls below zero we recommend protecting the central heating system with anti freeze liquid and installing t...

Page 23: ...and that the manometer indicates a pressure of 1 1 2 bar make sure the air valve cap is open and that the system is well deaerated switch the boiler on and check correct ignition make sure the gas ma...

Page 24: ...minating resistance R8 The connector X5 is used for the connection to the relay board The connector X6 is for connection to a personal computer The connector X8 is used for software updating operation...

Page 25: ...he type of gas being used S3 Boiler type Establishes the boiler type and its functioning mode 0 combi 1 24 kW storage tank 2 28 kW storage tank 3 32kW storage tank 0 3 2 S4 Power block Establishes the...

Page 26: ...0 P5 Relay 3 optional The boiler is set up for functioning with the relay P C B optional which can be configured 0 Off 1 Chiller remote activation 2 General alarm 3 CH phase active 4 External gas val...

Page 27: ...be adjusted must not be lower than that stated in the tables par 3 18 Adjustment any of the boiler maximum heat output in central heating phase To adjust the maximum heat output during the heating ph...

Page 28: ...tion of approx 10 seconds N B during self check the boiler remains off including signalling 3 15 SOLAR PANELS COUPLING FUNCTION In the event of integration of DHW heating with solar panel systems for...

Page 29: ...the guard a 3 Unhook the decorative frame c from the relative lower retainers 4 Remove the decorative frame c from the cas ing e 5 Loosen the 2 front screws d that fasten the casing 6 Loosen the 2 lo...

Page 30: ...30 3 5 6 6 7 8 8 f f e INSTALLER USER MAINTENANCE TECHNICIAN...

Page 31: ...7 22 0 18920 2 49 7 43 75 8 1 86 18 61 189 8 1 83 22 76 232 1 21 0 18060 2 38 6 82 69 6 1 78 17 24 175 8 1 75 20 92 213 4 20 0 17200 2 27 6 24 63 7 1 70 15 91 162 3 1 67 19 18 195 6 19 0 16340 2 17 5...

Page 32: ...eat output useful kW kcal h 11 2 9632 Efficiency at nominal heat output 94 3 Efficiency at 30 nominal heat output load 91 5 Heat loss at case with burner On Off 0 0 0 53 Heat loss at flue with burner...

Page 33: ...odel code Sr N Serial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH m...

Page 34: ......

Page 35: ......

Page 36: ...Europe S r o 059051 Poprad Matejovce SK Tel 421 524314311 Fax 421 524314316 IMMERGAS SPA ITALY CERTIFIED COMPANY UNI EN ISO 9001 2015 Design manufacture and post sale assistance of gas boilers gas wat...

Reviews: