DIP switches at the bottom rear of the controller can be set on site to suit the application.
DIP switch
Function
ON position
OFF position
1
Fan control
Fan control is temperature dependent in all
operating modes
Fan control in normal operation is
temperature independent
2
Operating mode changeover via
external switch
Changeover between normal operation and
energy saving mode
Changeover between normal operation and
standby
3
Action of switch for externally
operated mode changeover
Changeover activated when contact of
switch is closed
Changeover activated when contact of
switch is open
4
Standby
Frost protection disabled
Frost protection enabled
5
Switching differential
1K in heating mode, 0.5K in cooling mode
4K in heating mode, 2K in cooling mode
6
Dead zone in normal operation
2K
5K
= factory settings
--o--o--O--O--O--o--o--
CWR 25 TO 85 WIRING DIAGRAM
B
Brown
H
Heat/heater
R
Red
SH
Heater supplementary
O
Orange
EH
Heater electric
Y
Yellow
TP1
Thermal protector
G
Green
TP2
Thermal fuse
BL
Blue
RL
Relay
V
Violet
T1
Thermostat de-ice
GRY
Grey
T2
Thermostat supplementary
W
White
LK
Link
BK
Black
PCB1
Condensate control
P
Pink
RT
Remote thermostat
T
Turquoise
F
Fuse
HT
High temperature
S1
Condensate sensor
M1
Motor fan
C
Capacitor
M2
Pump
V1
Valve cool
M3
Vane motor
V2
Valve heat
AC
Air conditioner
CC
Control
HP
Heat pump
RV
Reversing valve
---
Not supplied