2 / 15
Nemo SX - Multifunction state module
Cat. N°:
SXMC02
4. PREPARATION
–
CONNECTION
(continued)
Terminals:
. Terminal depth: 8 mm.
. Stripping length: 8 mm
Screw head:
. Mixed, slotted and Pozidriv n°1 (UNI7596 type Z1).
Recommended tightening torque:
. 1 Nm.
Recommended tools:
. For the terminals: Pozidriv
n°1 or flat screwdriver 4 mm.
. For fixing: flat screwdriver 5.5 mm (6 mm maximum).
. For configuration DIP switches: flat screwdriver 2 mm
Conductor type:
Copper cable
Without ferrule
With ferrule
Rigid
Cable
1 x 0,5 mm² to 1,5 mm²
2 x 1,5 mm²
-
Flexible
Cable
1 x 0,5 mm² to1,5 mm²
2 x 1,5 mm²
1 x 0,5 mm² to 1,5 mm²
2 x 1,5 mm²
Wiring diagrams:
Inputs from voltage-free SPST NO contacts
4. PREPARATION
–
CONNECTION
(continued)
Module configuration:
. Configuration is possible in two ways:
1. remotely, via Nemo SX Configuration software (module firmware
version ≥ 2.0.2 [production date ≥ 18W49]
& Configuration software
≥ 1.05.00).
2. locally, via 4 DIP switches on the left side of the Nemo SX
module. Dipswitches may be manipulated by a screwdriver
Configuration allows to set:
- information type
- LED behaviour
. Default configuration (switches in 0000 position)
This configuration allows you to make all settings, according to the
function you need, remotely via Nemo SX configuration software
without actuate any switch (module firmware version ≥ 2.0.2
[production date ≥ 18W49]
& Configuration software ≥ 1.05.00).
It is however always possible configure the module by manually
actuating micro-switches.
Possible configurations (done locally or remotely) are listed as
shown below.
. Table of possible configurations
Note 1:
Steady LED
Blinking LED
LED off
Technical data sheet: IDP000169EN_04
Updated: 30/09/2020
Created: 31/08/2017