User manual Elba

www.igloo.pl

6. SERVICE

6.1. Fault identi

fi

 cation and repair

In case of any dif

fi

 culties during actuation of the device or during its exploitation, please return to these chapters in this ma-

nual, which explain the performed operation. This aims to ensure that the device is properly operated. If you still experience 
dif

fi

 culties, the following hints will help you solve the problem.

The device is not working... – Make sure that:

•  The device is connected to the supply network
•  Voltage and frequency in the network are compliant with those recommended by the producer 230V/50Hz
•  The main switch is turned on
•  Thermostat is switched on (Concerns the Igloo thermostat – If only two dots are displayed on the screen – turn on the thermo-

stat)

The device is operating, the lighting is switched off... – Make sure that:

•  The lighting switch is on
•  Fluorescent lamp or the starter of the device are not burnt 

The device does not reach the proper temperature, the lighting is on...– Make sure that:

•  The main switch is on
•  Temperature setting on the thermostat is properly set
•  The thermostat is operating properly  
•  Make sure that the condenser is not 

fi

 lthy, and clean the condenser when necessary

•  Ambient temperature does not exceed 25ºC 
•  Enough time has passed for products to be cooled
•  Too much fresh food has been placed in the cabinet and the maximum freezing capability has not been exceeded
•  Door of the devices close properly and whether the seal adheres to the body of the device
•  Ventilation holes of the device are not blocked

(This concerns the  “IGLOO” thermostat) thermostat displays C0 or C1 or C2 instead of displaying temperature:
This situation shall occur, when one of temperature regulation sensors has been destroyed. The following messages 
may be displayed in such case:

•  C0 – temperature sensors inside the chamber are damaged – call authorized service
•  C1 – failure of evaporator sensor - call authorized service
•  C2 – failure of condenser alarm sensors (or failure of second evaporator sensor) – call authorized service

(This concerns the “IGLOO” thermostat) The device is working, sound signalling is activated...– Make sure that:

•  The condenser is clean, if necessary – clean the condenser
•  Condenser ventilator is working properly
•  Ambient temperature does not exceed 25ºC

The device is working too loud...– Make sure that:

•  The device is standing stably and is properly levelled
•  Furniture adjoining the device do not vibrate when the compressor is working
•  Internal elements have been properly mounted

Steam precipitation on glasses of the device is a normal phenomenon in case of high relative air 
humidity exceeding 60% and does not require calling the service!

Noises made by the operating device are a normal phenomenon. The devices are equipped with venti-
lators, engines and compressors, which turn on and off automatically

 Each compressor makes certain 

noises when operating. These sounds are made by the aggregate engine and by cooling agent 

fl

 owing through the circuit. This phenomenon constitutes a technical feature of cooling devices 

and it does not signify their faulty work. 

Elements of device can corrode when improper used and maintenance. To avoid that please 
follow the rules:

• Do not allow contact of the surface of the device with substances  containing chlorine and / or baking 

soda in different varieties, which destroy the protective layer and components of the device (also 
includes various stainless steel)

Summary of Contents for ELBA

Page 1: ...naczenie Elba jest uniwersalnym urz dzeniem przeznaczonym do ekspozycji i przechowywania r norodnych produkt w mro o nych Elba ma zastosowanie w zak adach gastronomicznych cukierniach i sieciach sklep...

Page 2: ...bwodu elektrycznego z gniazdem wtykowym z ko kiem ochronnym w g PBUE Gniazdo winno by zabezpieczone bezpiecznikiem zw ocznym odpowiedniej warto ci ELBA C10 Uruchomienie urz dzenia mo e nast pi tylko p...

Page 3: ...m z rozruchem agregatu ch odniczego OSTRZE ENIE Chroni przed uszkodzeniem obw d ch odniczy Umie ci wtyczk przewodu przy czeniowego bezpo rednio w gnie dzie wtykowym zabrania si pod czania urz dzenia p...

Page 4: ...ktrycznych Utrzymywa skraplacz w czysto ci Zanieczyszczenia mog spowodowa przegrzanie spr arki i w efek cie doprowadzi do awarii urz dzenia co nie jest obj te gwarancj 4 1 Regulacja temperatury Obs ug...

Page 5: ...czas czynno ci konserwuj cych nale y sprawdzi czy drzwi zamykaj si w a ciwie Pr ba umie ci kartk papieru pomi dzy uszczelk a obudow i zamkn drzwi Papier powinien stawia wyczuwalny op r przy pr bie wyc...

Page 6: ...zenia nie s zablokowane Dotyczy term IGLOO Termostat wy wietla C0 lub C1 lub C2 zamiast temperatury Sytuacjatakamamiejsce je elizosta uszkodzonyjedenzczujnik wregulatoraw wczasmog pojawi si nast puj c...

Page 7: ...adres i numer telefonu wraz z numerem kierunkowym do Pa stwa Powy szy rysunek przedstawia pogl dow tabliczk znamionow a dane w niej zawarte s danymi przyk adowymi nieodnosz cymi si do ELBY Rys 7 Tabl...

Page 8: ...i Wyj cie z funkcji nast puje automatycznie po ok 3 sek R czne odszranianie przycisk nr 2 pozwala na w czenie cyklu odszraniania w dowolnym momencie pracy urz dzenia niezale nie od funkcji automatyczn...

Page 9: ...circulation The cabinet is equipped with auto matic defrosting automatic condensate evaporation and electronic thermostat optionally cooperating with temperature recording module enabling to record a...

Page 10: ...ric circuit with plug in socket with protecting pin according to PBUE Regulations concerning Electric Equipment Construction The socket should be protected with time delay cut out of proper value ELBA...

Page 11: ...n the device It is recommended to avoid unnecessary opening of the doors The device should be placed in a dry place not insolated and well ventilated ensuring proper air circulation min 10 cm distance...

Page 12: ...minutes which enables free opening of the doors Avoid unnecessary opening of the doors and leaving them open for a longer period of time Keep the condenser clean Impurities may lead to overheating of...

Page 13: ...intenance services it is necessary to check whether doors close in a proper manner Test place a sheet of paper between the seal and the casing and close the door The paper should pose felt resistance...

Page 14: ...isplaying temperature This situation shall occur when one of temperature regulation sensors has been destroyed The following messages may be displayed in such case C0 temperature sensors inside the ch...

Page 15: ...the problem Your exact address and telephone number with the code number The above figure shows a demonstrative data plate and the data stated on the plate are exemplary data which are not related wit...

Page 16: ...utomatically after about 3 seconds Manual defrosting switch No 2 enables to initiate the defrosting cycle at any moment when the device is working re gardless of the automatic defrosting function the...

Page 17: ...lage Elba ist mit dem innerenAggregat und gezwungenem Luftumlauf ausgestattet Der Schrank ist mit der automatischen Entfrostung und elektronischem optionalem Thermostat ausgestattet der dazu gedacht i...

Page 18: ...an separatem richtig durchgef hrtem Stromkreis mit Steckdose mit Schutzbolzen nach PBUE Die Steckdose sollte entsprechend abgesichert sein mit einer getrennten Sicherung ELBA C10 Die Anlage kann in B...

Page 19: ...gen eingestellt werden Die Anlage funktioniert richtig in einem Umgebung in dem die Temperatur der Klimaklasse die auf dem Typenschild angegeben ist entspricht Die Funktionsf higkeit der Anlage kann v...

Page 20: ...sen worden sind ist es verboten diese gewaltig zu fnnen versuchen Im Inneren der Anlage entsteht der Unterdurck der in 1 2 Minuten ausgegleichen wird Danach ist es m glich die T ren zu ffnen Falls es...

Page 21: ...haben Bei den Wartungsarbeiten ist es pr fen ob Sich die T ren richtig schliessen Probe den Papierzettel zwischen die Dichtung und das Geh use anbringen und die T ren schlies sen Das Papier soll den W...

Page 22: ...dem Thermostat ist C0 oder C1 bzw C2 statt Temperatur gezeigt Wir haben damit zu tun wenn einer von F hlern des Temperaturreglers besch digt wird In dieser Situation werden folgende Hinweisen gezeigt...

Page 23: ...onnummer zusammen mit Durchwahl Auf dieser Abbildung ist das anschaunliche Ty penschild dargestellt und hier erteilte Angaben sind als Beispiel zu vorstehen die Elba nicht betreffen Abb 7 Typenschild...

Page 24: ...m Betrieb erfolgt automatisch nach 3 Sekunden Handentrostung die Taste Nr 2 erm glicht dass der Entrostungsbetrieb in beliebiger Weile w hrend der Arbeit der An lage eingeschaltet wird unabh ngig von...

Page 25: ...25 2 25 2 1 25 2 2 25 2 3 26 3 26 3 1 26 3 2 27 4 27 4 1 28 5 28 5 1 28 6 30 6 1 30 6 2 31 7 32 7 1 IGLOO 32 1 2 2 1 ELBA Elba 18 C 12 C 15 C 25 C 60 2 2 ELBA ELBA 6 1 26 ELBA ru 1 26 2 27 3 27 4 29...

Page 26: ...A 2 9 51 24 10 3 500 6 470 x510 1 30 3 3 1 PBUE ELBA C10 1 2 3 4 5 6 7 8 9 10 1 NS 069 XXX MASA xxx NAPIECIE ZNAM xxx MOC ZN O W xxx MOC GRZA EK xxx NAPIECIE ZNAM xxx KLASA URZADZ xxx Typ NAZWA UR Z...

Page 27: ...ru 27 Elba www igloo pl 3 2 1 4 26 I 2 1 2 27 II 2 3 27 3 1 27 3 3 27 32 3 2 27 4 10 2 1 2 3 4 3 1 2 3 7 32 40 C 2 1 2 3 1 2 3 4...

Page 28: ...ru 28 Elba www igloo pl 2 1 2 4 1 Igloo 7 32 5 5 1...

Page 29: ...ru 29 Elba www igloo pl 2 1 4 5 7 6 3 3 10 4 3 9 8 2 1 7 31 1 2 3 4 5 6 7 8 9 10 5 1 2 4 6...

Page 30: ...ru 30 Elba www igloo pl 6 6 1 230 50 Igloo 25 C IGLOO C0 C1 C2 C0 C1 C2 IGLOO 25 C 60...

Page 31: ...ru 31 Elba www igloo pl 6 2 IGLOO 48 14 662 19 56 48 605 606 071 e mail serwis igloo pl 6 1 Igloo 7 31 NS ELBA 7 IGLOO...

Page 32: ...ru 32 Elba www igloo pl 7 7 1 IGLOO 8 Igloo 3 3 2 www igloo pl 1 2 3 4 5 6 2 1 3 4 6 5...

Reviews: