33
System- / Assignment table (in correct operating state):
Tighten
relay
open (no power, state of rest)
LLW output
Probe ̲̲̲̲ submerged
Probe ̲̲̲̲ emerged
HHW output
Probe ̲̲̲̲ emerged
Probe ̲̲̲̲ submerged
Output 1
Probe ̲̲̲̲ submerged / emerged *
Probe ̲̲̲̲ submerged / emerged *
Output 2
Probe ̲̲̲̲ submerged / emerged *
Probe ̲̲̲̲ submerged / emerged *
Output 3
Probe ̲̲̲̲ submerged / emerged *
Probe ̲̲̲̲ submerged / emerged *
Output 4
Probe ̲̲̲̲ submerged / emerged *
Probe ̲̲̲̲ submerged / emerged *
Output 5
Probe ̲̲̲̲ submerged / emerged *
Probe ̲̲̲̲ submerged / emerged *
Output 6
Probe ̲̲̲̲ submerged / emerged *
Probe ̲̲̲̲ submerged / emerged *
Output 7
Probe ̲̲̲̲ submerged / emerged *
Probe ̲̲̲̲ submerged / emerged *
* delete wrong state
Programming example:
Start:
press “o.k.” (to access the menu)
press ▼ or ▲ until 4.2 Password is displayed in top row
press “o.k.”
Enter Password:
Display:
000
▲
100 “o.k.” 100
▲ ▲ 120
“o.k.” 120
▲ ▲ ▲ 123
“o.k.”
The items 4.3, 4.4, and 4.5 can now be accessed!
Low-water-level-alarm set to probe 2:
enter password, then
press ▼ or ▲ until 4.4 LLW Alarm is shown
press “o.k.”
press ▼ or ▲ until “on” is shown
press “o.k.”
press ▼ or ▲ until 00 is shown (0 indicates the first digit of the desired probeʼs number)
press “o.k.”
press ▼ or ▲ until 02 is shown (2 indicates the second digit of the desired probeʼs number)
press “o.k.”
(again 4.4 LLW Alarm is displayed)
The programming is finished.