24
MU:
Material switch box
Stainless steel (1.4404/316L)
Protection type
Front side IP65
Working temperature:
0°C to + 85°C
Humidity
non-condensing
Voltage supply
18V ‒ 36V; 24V DC / 2W short-circuit-proof via lead
Current consumption
50mA @ 24V
Electrode voltage
3 Vss
Interface
CAN-Bus according to DIN ISO 11898, CANopen protocol
Self-Test
every 3 s
CU:
2x21 pole Screw terminal strip:
Voltage supply
24V DC ± 10% / 24 W
through 1 or 2 separate power supply unit(s)
Current consumption
200mA
Interfaces
CAN-Bus according to DIN ISO 11898, CANopen protocol
4 mA ‒ 20 mA (load < 500Ohm)
not galv. decoupled
7 SPDT output contacts freely programmable
(Probe ‒ switch contact)
1 SPDT output contact responding to device errors
1 SPDT output contact responding to water level alarm (HW
and/or LW); the probes for LW and/or HW can be freely
choosen
Material
PC-GF V-0
Protection type
Housing: IP40
Terminals: IP20
Connection
Two 21-terminal strips to 2.5 mm²
Display
LCD display with 2 16-character lines
Input / Programming
4 keys
Working temperature:
0°C to +55°C
Self-Test
every 3 s