34
fill level control (via 2 contacts) by way of pump control:
Probe 3 emerged: start pump / probe 13 submerged: stopp pump / via output 5
The pump contactor is connected to the contacts Out5:34 and Out5:36
enter password, then
press ▼ or ▲ until 4.3 Relay setup is shown
press “o.k.”
press ▼ or ▲ until 5 is shown
press “o.k.”
press ▼ or ▲ until “on” is shown
press “o.k.”
press ▼ or ▲ until 00 is shown (0 indicates the first digit of the desired timeʼs number)
press “o.k.”
press ▼ or ▲ until 00 is shown (0 indicates the second digit of the desired timeʼs number)
press “o.k.”
(the desired delaytime should be displayed)
press ▼ or ▲ until 00 is shown (0 indicates the first digit of the desired probeʼs number)
press “o.k.”
press ▼ or ▲ until 03 is shown (3 indicates the second digit of the desired probeʼs number)
press “o.k.”
(the desired probe (03 in this example) should be displayed)
press “o.k.”
press ▼ or ▲ until STEAM is shown
press “o.k.”
press ▼ or ▲ until 00 is shown (0 indicates the first digit of the desired timeʼs number)
press “o.k.”
press ▼ or ▲ until 00 is shown (0 indicates the second digit of the desired timeʼs number)
press “o.k.”
(the desired delaytime should be displayed)
press ▼ or ▲ until 10 is shown (1 indicates the first digit of the desired probeʼs number)
press “o.k.”
press ▼ or ▲ until 03 is shown (3 indicates the second digit of the desired probeʼs number)
press “o.k.”
The programming is finished.
Logical correlations are set automatically:
- If in the first part of the programming the output is to be active (ON), then in the second part
OFF is set automatically.
- If the output is to be active, if the probe emerges (STEAM) (1st part of the programming), then
in the 2
nd
part WATER is preset.
Thus the programming ends with the affirmation of the 1-digit of the probe. The settings are
saved and the display returns to the menu item “4.3 Relay setup”.