8 Set-up
Before set-up, the units are to be mounted (
9) and electrically connected (
11).
8.1 DTE830
DTE830 is set using the ReaderStart software. The software and the software manual are available in
the download area of the DTE830:
The following functions are described in detail in the software manual.
Connecting with the software
Connect the DTE830 using the ReaderStart software:
u
Connect the DTE830 to the PC via the EVC895 connection cable.
u
Start the ReaderStart software.
u
Establish a connection between ReaderStart and the DTE830.
w
The PC and the DTE830 must be in the same IP address range "192.168.0.xxx".
w
The default IP address of the DTE830 is "192.168.0.1".
Setting the software
u
When using extension gates (
6): Set the IP addresses in the ReaderStart
software as shown in the table.
w
See ReaderStart software manual, chapter "Function group [KO] communication".
Gate number
IP address
Description
1
192.168.0.1
DTE830 gate 1
2
192.168.0.11
DTE830 gate 2
3
192.168.0.21
DTE830 gate 3
4
192.168.0.31
DTE830 gate 4
5
192.168.0.41
DTE830 gate 5
6
192.168.0.51
DTE830 gate 6
7
192.168.0.61
DTE830 gate 7
8
192.168.0.71
DTE830 gate 8
9
192.168.0.81
DTE830 gate 9
10
192.168.0.91
DTE830 gate 10
u
Set the following values in the expert settings 1 (E1) of the ReaderStart software:
w
See ReaderStart software manual, chapter "Function group [E1] Expert settings 1".
u
Enable the ports [1..4].
u
Set the cable attenuation to “5 dB”.
u
Set the antenna type [user antenna] to "8.5 dBiC".
u
Set the slider [power] of port "1..4" to "30 dBm".
u
Click on the [Set] button.
w
The settings are saved.
Activating compatibility mode
Compatibility mode increases compatibility with connected devices and is necessary for operation.
Enabling the compatibility mode: