![background image](http://html1.mh-extra.com/html/ifm/vse153/vse153_device-manual_3884360014.webp)
14
Rotational
speed
Real
4 bytes
Trigger - rotational speed
Reference
value
Real
4 bytes
Trigger - reference value
Warning
alarm
Real
4 bytes
Limits - warning alarm (relative)
Damage
alarm
Real
4 bytes
Limits - damage alarm (relative)
Counter
<counter name>
DINT
4 bytes
Counter value (in seconds)
Alarms
<alarm name>
Byte
1 byte
Alarm state (0, 1)
General
Variant
Byte
1 byte
Current variant (0���31)
System mode
Byte
1 byte
System mode:
0 : self-test
1: supervise (normal monitoring)
2: set-up (parameter setting)
3: measure (spectrum, raw data)
4: start-up (system booting)
Self-test result
Byte
1 byte
Binary bit pattern
0: sensors OK
1: sensor 1 self-test failed
2: sensor 2 self-test failed
4: sensor 3 self-test failed
8: sensor 4 self-test failed
Current queue level
Byte
1 byte
Current level of the fieldbus
communication
Queue overflow counter
DINT
4 bytes
Overflow counter of the fieldbus
communication
Checksum error counter
DINT
4 bytes
Checksum error counter of the fieldbus
communication
Output (PLC)
External inputs
<input name>
Real
4 bytes
Set value of the external input (Exter-
nal_xx)
Objects
<object name>
Base line
Real
4 bytes
Limits - set base line in SI unit (m/s², m/s,
m) to adapt the limits
General
Variant
Byte
1 byte
Set current variant (0���31)
Do self-test
Byte
1 byte
Do self-test (≠ 0)
Summary of Contents for VSE153
Page 3: ...UK 3...