Firmware and operating software → download area www.ifm.com
A description of all firmware parameters and their meaning → VES004 PC 

software manual�

5.2  Functional overview

With the device 

 

– vibration monitoring (total vibration to ISO)

 

– condition monitoring (condition-based monitoring on the basis of vibration 

characteristics) 

 

– machine protection/process monitoring (monitoring vibration characteristics 

in real time with a very fast response time up to 1 ms) 

can be implemented�
Monitoring of 

 

– up to 24 objects (indicators for different machine parts, vibration 

characteristics or process values) 

 

– dynamic values within the time range (e�g� v-RMS to ISO)

 

– dynamic values within the frequency range FFT or HFFT (e�g� imbalance or 

rolling element bearing)

 

– process values (analogue signals) for current value above or below the limit

The device has an internal history memory (600,000 values) with real-time clock 

and flexible memory interval per object� The memory is a ring memory (FIFO)�
Up to 32 counters can be configured to measure the duration of exceeding the 

limit and/or operating times�
The signals at the inputs are permanently picked up and continuously monitored 

according to the set parameters�  

With objects within the frequency range (imbalance, rolling element bearing ���) the 

multiplex mode is used for monitoring� 

With objects within the time range (v-RMS, a-RMS and a-Peak) all 4 dynamic 

inputs are monitored simultaneously and without interruption�
The two outputs OU1/2 can be used for alarms� The respective object states per 

sensor are also indicated via the 4 sensor LEDs�
The system LED displays the operating status of the device�
Parameter setting of the monitoring tasks and alarming is effected by the VES004 

software� The software allows to display and record the current measured values, 

spectra and time signals (online data)�
Via the Ethernet interface of the device, networking is possible to visualise data 

(measured values, alarm states, ���) in other systems (e�g� SCADA, MES, ����)�

Summary of Contents for VSE153

Page 1: ...Device manual Diagnostic electronics with Modbus TCP interface for vibration sensors VSE153 80270599 00 03 2019 UK...

Page 2: ...data model 12 8 3 Register 15 8 3 1 Modbus TCP device identification register 15 8 4 Modbus TCP register mapping input FC4 15 8 5 Modbus TCP input function code 15 8 6 Modbus TCP register mapping outp...

Page 3: ...UK 3...

Page 4: ...instructions or the technical data are not adhered to personal injury and or damage to property may occur The manufacturer assumes no liability or warranty for any consequences caused by tampering wi...

Page 5: ...ts Adhere to the data indicated in the data sheets and in the manual If the handling specifications and safety instructions for configuration installation and operation indicated in the documentation...

Page 6: ...ng interface can be used for parameter setting of the device online data monitoring reading the history memory firmware update The Modbus TCP ports are used for the communication between the diagnosti...

Page 7: ...time clock and flexible memory interval per object The memory is a ring memory FIFO Up to 32 counters can be configured to measure the duration of exceeding the limit and or operating times The signa...

Page 8: ...ables can be installed for example in cable ducts or on cable bridges Data corruption and loss A minimum distance between the cabling and possible sources of interference e g machines welding equipmen...

Page 9: ...61340 5 1 In order to eliminate electrostatic charges the device may only be operated on a grounded DIN rail 7 Electrical connection The national and international regulations for the installation of...

Page 10: ...l 11 14 18 22 BU GND IEPE GND 12 13 17 21 BK test not connected n c not connected n c Terminal 1 supply L When using an IEPE input 24 V DC 20 Integrated Electronics Piezo Electric The ground GND of th...

Page 11: ...dbus TCP 8 1 Characteristics Modbus TCP Request Parameters Register access only acyclical r w Register addressing based on 1 Transmission rate 100 Mbits s 10 Mbits s Protocols and minutes Modbus TCP I...

Page 12: ...Hex0001 internal error Hex0002 calculation error Hex0004 speed out of range Hex0008 speed unstable Hex0010 invalid base line Hex0020 invalid reference value 1 Hex0040 invalid reference value 2 Hex010...

Page 13: ...Trigger reference value Warning alarm Real 4 bytes Limits warning alarm relative Damage alarm Real 4 bytes Limits damage alarm relative Base line Real 4 bytes Limits base line in SI unit m s m s m Up...

Page 14: ...em booting Self test result Byte 1 byte Binary bit pattern 0 sensors OK 1 sensor 1 self test failed 2 sensor 2 self test failed 4 sensor 3 self test failed 8 sensor 4 self test failed Current queue le...

Page 15: ...name ifm electronic 39030 R 20 product name VSE153 39050 R 2 production status of the unit AA 39052 R 10 firmware version V1 0 0 39062 R 2 serial Number defined in the product process 39064 R 20 shor...

Page 16: ...03 Illegal data value Code 04 Server device failure 9 Factory setting 9 1 General factory setting Request Parameter Parameter set none Host name no name assigned IP address 192 168 0 1 TCP IP port 33...

Page 17: ...description of all parameters and possible configurations we refer you to the VES004 software manual 11 Operating and display elements For quick identification of error states the device has two diagn...

Page 18: ...thernet ports RJ45 sockets with one integrated link and activity LED each Designation Colour Status Description Link green on connected at ports 1 2 green off not connected at ports 1 2 Activity yello...

Page 19: ...nge flashing firmware image is loaded to the RAM orange on firmware image is written to the flash green flashing 2 s approx 2 Hz firmware image has been written correctly to the flash orange flashing...

Reviews: