background image

UK

11

If the DC circuit is to be grounded (e�g� due to national regulations), the PELV 

criteria must be adhered to (protective extra-low voltage, circuit electrically isolated 

from other circuits)�
Sensor and diagnostic electronics supply are not electrically isolated�

7.3  Ethernet connection

The RJ45 config socket is used for the connection to the Ethernet�  

Ethernet cables can be supplied as accessories, e�g�: 
cross-over cable, 2 m, article no� EC2080 
cross-over cable, 5 m, article no� E30112

8  Modbus TCP

8.1  Characteristics Modbus TCP

Request

Parameters

Register access

only acyclical r/w

Register addressing

based on 1

Transmission rate

100 Mbits/s, 10 Mbits/s

Protocols and minutes

Modbus TCP/IP

Data format

big-endian

Modbus TCP/IP
Max� input and output process image

1024 bytes (512 registers)

Configuration

via PC with configuration tool: VES004

Max� number of socket connections

8x Modbus TCP

Register filing of the input data

analogue input register 16 bits (r)

Register filing of the output data

analogue holding register 16 bits (r/w)

Supported function codes

FC3, FC4, FC6, FC16

Write max� byte length for registers

1���123 registers

Read max� byte length for registers

1���125 registers

Summary of Contents for VSE153

Page 1: ...Device manual Diagnostic electronics with Modbus TCP interface for vibration sensors VSE153 80270599 00 03 2019 UK...

Page 2: ...data model 12 8 3 Register 15 8 3 1 Modbus TCP device identification register 15 8 4 Modbus TCP register mapping input FC4 15 8 5 Modbus TCP input function code 15 8 6 Modbus TCP register mapping outp...

Page 3: ...UK 3...

Page 4: ...instructions or the technical data are not adhered to personal injury and or damage to property may occur The manufacturer assumes no liability or warranty for any consequences caused by tampering wi...

Page 5: ...ts Adhere to the data indicated in the data sheets and in the manual If the handling specifications and safety instructions for configuration installation and operation indicated in the documentation...

Page 6: ...ng interface can be used for parameter setting of the device online data monitoring reading the history memory firmware update The Modbus TCP ports are used for the communication between the diagnosti...

Page 7: ...time clock and flexible memory interval per object The memory is a ring memory FIFO Up to 32 counters can be configured to measure the duration of exceeding the limit and or operating times The signa...

Page 8: ...ables can be installed for example in cable ducts or on cable bridges Data corruption and loss A minimum distance between the cabling and possible sources of interference e g machines welding equipmen...

Page 9: ...61340 5 1 In order to eliminate electrostatic charges the device may only be operated on a grounded DIN rail 7 Electrical connection The national and international regulations for the installation of...

Page 10: ...l 11 14 18 22 BU GND IEPE GND 12 13 17 21 BK test not connected n c not connected n c Terminal 1 supply L When using an IEPE input 24 V DC 20 Integrated Electronics Piezo Electric The ground GND of th...

Page 11: ...dbus TCP 8 1 Characteristics Modbus TCP Request Parameters Register access only acyclical r w Register addressing based on 1 Transmission rate 100 Mbits s 10 Mbits s Protocols and minutes Modbus TCP I...

Page 12: ...Hex0001 internal error Hex0002 calculation error Hex0004 speed out of range Hex0008 speed unstable Hex0010 invalid base line Hex0020 invalid reference value 1 Hex0040 invalid reference value 2 Hex010...

Page 13: ...Trigger reference value Warning alarm Real 4 bytes Limits warning alarm relative Damage alarm Real 4 bytes Limits damage alarm relative Base line Real 4 bytes Limits base line in SI unit m s m s m Up...

Page 14: ...em booting Self test result Byte 1 byte Binary bit pattern 0 sensors OK 1 sensor 1 self test failed 2 sensor 2 self test failed 4 sensor 3 self test failed 8 sensor 4 self test failed Current queue le...

Page 15: ...name ifm electronic 39030 R 20 product name VSE153 39050 R 2 production status of the unit AA 39052 R 10 firmware version V1 0 0 39062 R 2 serial Number defined in the product process 39064 R 20 shor...

Page 16: ...03 Illegal data value Code 04 Server device failure 9 Factory setting 9 1 General factory setting Request Parameter Parameter set none Host name no name assigned IP address 192 168 0 1 TCP IP port 33...

Page 17: ...description of all parameters and possible configurations we refer you to the VES004 software manual 11 Operating and display elements For quick identification of error states the device has two diagn...

Page 18: ...thernet ports RJ45 sockets with one integrated link and activity LED each Designation Colour Status Description Link green on connected at ports 1 2 green off not connected at ports 1 2 Activity yello...

Page 19: ...nge flashing firmware image is loaded to the RAM orange on firmware image is written to the flash green flashing 2 s approx 2 Hz firmware image has been written correctly to the flash orange flashing...

Reviews: