SB1xxx SB2xxx SB3xxx SB4xxx SB5xxx SB6xxx SB7xxx SB8xxx SB9xxx SB03xx
Mechatronic flow
sensor
20
FOU = OFF 0
2
1
3
4
5
FOU = ON 130
120
100
UL
Err
Err
= FrP1
MAW
FSP1
FEP1
MEW
OL
100 120
[% MEW]
[% FrP1]
Fig. 18: Output characteristics frequency output, temperature
1:
Frequency signal
FSP1:
Frequency start point
2:
Temperature
FEP1:
Frequency end point
3:
Display range
FrP1:
Frequency signal (Hz) for upper measured value
4:
Measuring range
MAW:
Initial value of the measuring range
5:
Scaled measuring range
MEW:
Final value of the measuring range
Err:
Error
OL:
Above the display range
10.3.3.1 Parameter setting via unit keys: Frequency signal
ü
Standard unit of measurement is selected: [EF] > [CFG] > [uni.x].
ü
Process value for OUT1 is selected: [EF] > [CFG] > [SEL1].
u
Select the [EF] > [CFG] menu.
u
Select [ou1] and set FRQ.
u
Call up the [main menu].
u
Select [FSP1] and set the lower measured value at which 0 Hz is output.
[FSP1] is only available for temperature measurement.
u
Select [FEP1] and set the upper measured value at which the frequency set at [FrP1] (= 100 %) is
output.
u
Select [FrP1] and set the frequency for the upper measured value in Hz.
10.3.3.2 Parameter setting via IO-Link: Frequency signal
ü
Standard unit of measurement is selected: [Parameter] > [Display setting] > [uni.x].
ü
Process value for OUT1 is selected: [Parameters] > [Output configuration] > [SEL1].
u
Call up [Parameters] > [Output Configuration].
u
Select [ou1] and set FRQ.
u
Call up [Parameters] > [Frequency Output 1].
u
Select [FrP1] and set the frequency for the upper measured value in Hz.
u
Call up [flow] or [temperature].
u
Select [FSP1 - TEMP] and set the lower measured value at which 0 Hz is output.
[FSP1] is only available for temperature measurement.
u
Select [FEP1_FLOW] / [FEP1_TEMP] and set the upper measured value at which the frequency
set at [FrP1] (= 100 %) is output.