background image

4

3  Function and features

The pressure monitor detects the system pressure and generates two output 

signals (2 NO with independently adjustable switch points:
• 

In case of increasing pressure OUT1 (OUT2) closes when the Set1 (Set2) 

value is reached�

• 

In case of decreasing pressure OUT1 (OUT2) opens when the value „Set1 

(Set2) minus hysteresis“ is reached.

The hysteresis is fixed (2% of value of measuring range).

Applications

Type of pressure: relative pressure

Order no.

Measuring range

Permissible 

overload pressure

Bursting

pressure

bar

PSI

bar

PSI

bar

PSI

PK7520

0���400

0���5 800

600

8 700

1 600

23 200

PK7521

0���250

0���3 625

400

5 800

1 000

14 500

PK7522

0���100

0���1 450

200

2 900

1 000

14 500

PK7523

0���25

0���363

60

870

500

7523

PK7524

0���10

0���145

25

362

300

4 350

Avoid static and dynamic overpressure exceeding the given overload

pressure�

Even if the bursting pressure is exceeded only for a short time the unit can 

be destroyed (danger of injuries)!

If the cable length exceeds 30 m or if used outside buildings, there is a risk 

of overvoltage pulses from external sources� We recommend to use the 

unit in protected operating environments and to limit overvoltage pulses to 

max� 500 V�

4  Installation

Before mounting and removing the sensor, make sure that no pressure is 

applied to the system�

Summary of Contents for PK752 Series

Page 1: ...Operating Instructions Electronic pressure monitor PK752x 707882 00 03 2020 UK ...

Page 2: ...r indications Cross reference Important note Non compliance may result in malfunction or interference Information Supplementary note Contents 1 Preliminary note 2 1 1 Symbols used 2 2 Safety instructions 2 3 Function and features 4 4 Installation 4 5 Electrical connection 4 6 Setting Operation 5 ...

Page 3: ...product and keep it during the entire service life The product must be suitable for the corresponding applications and environmental conditions without any restrictions Only use the product for its intended purpose Functions and features Only use the product for permissible media Technical data If the operating instructions or the technical data are not adhered to personal injury and or damage to ...

Page 4: ... bar PSI PK7520 0 400 0 5 800 600 8 700 1 600 23 200 PK7521 0 250 0 3 625 400 5 800 1 000 14 500 PK7522 0 100 0 1 450 200 2 900 1 000 14 500 PK7523 0 25 0 363 60 870 500 7523 PK7524 0 10 0 145 25 362 300 4 350 Avoid static and dynamic overpressure exceeding the given overload pressure Even if the bursting pressure is exceeded only for a short time the unit can be destroyed danger of injuries If th...

Page 5: ...UT1 Pin 2 OUT2 1 locking ring 2 setting rings manually adjustable after unlocking 3 yellow LED Set1 value reached OUT1 ON 4 process connection G A tightening torque 25 Nm 5 setting marks 6 yellow LED Set2 value reached OUT2 ON 7 sealing FPM DIN 3869 14 8 internal thread M5 To obtain the setting accuracy Set the rings to the minimum value then set the requested value More information at www ifm com...