31
UK
Display
IO-Link event number
IO-Link PDV
alid
IO-Link device status Idx 36
Type of fault
Corrective measures
-/-* 0x5111 No
2** Supply voltage
too low�
►
Check / correct the
supply voltage�
►
In 2-wire operation:
Check / correct the
connected load�
SC1 0x8CB3 Yes
2** Excessive current
switching output 1�
►
Check switching output
1 for short-circuit or
excessive current;
remove the fault�
SC2 0x8CB4 Yes
2** Excessive current
switching output 2�
►
Check switching output
2 for short-circuit or
excessive current;
remove the fault�
Para 0x1810/
0x1Fxx
No
2** Parameter setting fault
via IO-Link; setting a
parameter outside the
permitted area�
►
Define parameter via the
IO-Link event number
0x1Fxx�
►
Change parameter
via IO-Link or setting
buttons�
►
Reset all parameters to
factory setting (→ 9.5.2).
OL
0x8C10 Yes
2** Process value too high�
►
Check / reduce system
pressure�
UL
0x8C30 Yes
2** Process value too low�
►
Check / increase system
pressure�
E100 0x5000 No
4** Internal sensor fault
detected�
►
Replace the unit�
W531 0x8CA1 Yes
2** Analogue output at the
upper limit (20�5 mA)�
►
Increase AEP value
if possible (if [OU2] =
[InEG] ASP value) or
reduce system pressure�