28
a) Finish calibration:
►
Briefly press [Mode/Enter]�
> [CAL] is displayed�
b) Change a 2nd point on the curve of measured values:
►
Set a second defined reference pressure in the system�
Minimum distance between the calibration points CP1 and CP2 = 5 % of
the final value of the measuring range�
►
Press [Set] for 5 s�
> The pressure measured by the unit is displayed�
►
Press [Set] until the set reference pressure is indicated (measured
pressure = reference pressure) or the corresponding analogue signal is
provided on OUT2�
Maximum correction value = ± 2 % of the final value of the measuring
range�
►
Briefly press [Mode/Enter]�
> [CP2] is displayed�
►
Briefly press [Mode/Enter]�
> [CAL] is displayed, the process is finished�
9.5 Service functions
9.5.1 Read min/max values for the system pressure
►
Select [HI] or [LO] and briefly press [Set]�
[HI] = maximum value, [LO] = minimum value�
Delete memory:
►
Select [HI] or [LO]�
►
Press and hold down [Set] until [----] is displayed�
►
Briefly press [Mode/Enter]�
9.5.2 Reset all parameters to factory setting
►
Select [rES]�
►
Press and hold down [Set] until [----] is displayed�
►
Briefly press [Mode/Enter]�
We recommend noting down your own settings before carrying out a reset
(→ 13 Factory setting).
9.6 Simulation function
9.6.1 Open menu level 3 (simulation)
►
Select [EF] and briefly press [Set] (= to open menu level 2)�
►
Select [SIM] and briefly press [Set] (= to open menu level 3)�
> [SEL] is displayed�