24
►
Select [diS] and set the update rate and orientation of the display:
-[d1]: update of the measured values every 50 ms�
-[d2]: update of the measured values every 200 ms�
-[d3]: update of the measured values every 600 ms�
-[rd1], [rd2], [rd3]: display as with d1, d2, d3; rotated by 180°�
-[OFF] = The measured value display is deactivated in the Run mode�
When one of the buttons is pressed the current measured value is
displayed for 15 s� Pressing the [Mode/Enter] button again activates
the display mode� The LEDs remain active even if the display is
deactivated�
Error messages are displayed even if the display is deactivated�
9.3 Set output signals
9.3.1 Set output functions
►
Select [OU1] and set the switching function:
-[Hno] = hysteresis function/normally open
-[Hnc] = hysteresis function/normally closed
-[Fno] = window function/normally open
-[Fnc] = window function/normally closed
►
Select [OU2] and set the function:
-[Hno] = hysteresis function/normally open
-[Hnc] = hysteresis function/normally closed
-[Fno] = window function/normally open
-[Fnc] = window function/normally closed
-[I] = current signal proportional to pressure 4…20 mA
-[InEG] = current signal proportional to pressure 20…4 mA
9.3.2 Set switching limits
►
Select [SP1] / [SP2] and set the value at which the output is set�
►
Select [rP1] / [rP2] and set the value at which the output is reset�
rPx is always lower than SPx� The unit only accepts values which are lower
than the value for SPx�