7
UK
Example Hno
1� For the output function [Hno] the output switches on when the set point [SPx]
is exceeded in case of a rising level�
2� If the level falls again, the output switches off as soon as the level is below the
reset point [rPx]� The reset point [rPx] is below the set point [SPx]�
1
2
[SPx] = set point; [rSPx] = reset point; HY = hysteresis
If the output function [Hnc] has been selected, set and reset point are exchanged�
The output switches off for rising level� If the level falls below [rPx] again, the
output switches on�
Switching status of the outputs
Output function
Level (L)
Output status
[Hno]
L > [SPx]
Closed
L < [rPx]
Open
[Hnc]
L > [SPx]
Open
L < [rPx]
Closed