15
UK
Environmental conditions
Application (according to EN 60654-1)
class C
Ambient temperature
for service life ≤ 87600 h
for service life ≤ 175200 h
-25���70 °C
10���40 °C
Max� perm� relative humidity
short time
permanent
5...95 %
5...70 %
Air pressure
80���106 kPa
Height above sea level
< 2000 m
Ionising radiation
not permissible
Salt spray
no
Protection rating (protected cable laying)
IP 67 / IP 69K
Degree of soiling
3
Approvals / tests
EMC
IEC 60947-5-2
Shock resistance (EN 60068-2-27)
30 g (11 ms)
Vibration resistance (IEC 60068-2-6)
10 g (10���55 Hz)
Safety classification
EN ISO 13849-1: 2015
category: 4
PL: e
IEC 61508
SIL 3
IEC 62061
SIL
cl
3
Mission time T
M
≤ 175200 h (20 years)
Safety-related reliability PFH
D
1�5E-09
Mechanical data
Installation
non flush mountable
Housing materials
PA
Tightening torque
0�8���2 Nm