6.2 Operating principle / features of the unit
The unit can be flexibly installed in tanks of different sizes�
2 outputs are available:
OUT1
Switching signal for level limit value/IO-Link
OUT-OP
Switching signal for level limit value (overflow prevention)
OUT1 can be freely configured, OUT-OP is fixed to NC and has a fixed hysteresis
(a few mm)�
6.2.1 Notes on the integrated overflow prevention
With the parameter [OP] (OP = overflow prevention), one of the upper measuring
segments is defined as integrated overflow prevention OP�
• The overflow prevention OP is the maximum limit of the measuring range�
The switch point [SP1] / [FH1] is always below [OP]�
• The overflow prevention OP is assigned to the output OUT-OP!
• Typically the overflow prevention OP reacts when the selected measuring
segment has been reached (a few mm before the set OP value)�
• The overflow prevention OP reacts immediately and without delay�
• The response of the overflow prevention OP is indicated on the display
("Full" and indication of the current level change every second)�