7.1 Other installation notes
• For mounting in plastic pipes/plastic tanks, the inside pipe diameter must at
least be 12�0 cm (4�8 inches)� Install sensor in the centre�
• For mounting in metal pipes the inside pipe diameter (d) must be at least:
Table 7-3
MEdI = CLW�1
MEdI = CLW�2, OIL�1
MEdI = OIL�2
[cm]
[inch]
[cm]
[inch]
[cm]
[inch]
d
4�0
1�6
6�0
2�4
10�0
4�0
7.1.1 Marking of the installation height
►
Fix the set installation height with the supplied
stainless steel tube clip�
If the sensor is removed from the fixture for main-
tenance reasons, the clip serves as a limit stop
when remounting the sensor� Thus an inadvertent
maladjustment of the sensor is excluded� This is in
particular necessary for the correct function of the
overflow prevention OP�
►
Fit the stainless steel tube clip using pliers�
►
Ensure a safe fit�
►
To remove the clip it has to be destroyed�