5 Installation
Using process adapters the unit can be adapted to different process connections
Adapters have to be ordered separately as accessories
Immersion depth of the sensor: min 12 mm in the pipe If you use the adapter
supplied as accessory the correct immersion depth is ensured
Mounting dimensions with
M12 adapter
Mounting dimensions with
G¼ adapter
Mounting dimensions with
G½ adapter
��
��
��
��
��
��
��
��
For optimum response times:
Orientation of the unit: Connector
►
against the flow direction of the
medium
Before installing and removing the unit: Ensure that no medium can leak at
the process connection
�
�
�
�
Grease the threads of the process connection (1), adapter (2) and nut (3)
►
Note: The sensor tip (A) must not be in contact with grease
Screw the suitable adapter into the process connection
►
Place the temperature sensor onto the adapter and tighten the nut Tightening
►
torque max 50 Nm Ensure that the unit is correctly oriented