9.5 User settings (optional)
9.5.1 Zero point calibration
Select [COF] and enter value Setting range:
►
-100100 °C in steps of 01 °C
-180 180 °F in steps of 01° F
The internal measured value "0" is shifted by this value
9.5.2 Setting of the delay time for OUT1
[dS1] = switch-on delay / [dr1] = switch-off delay
Select [dS1] or [dr1] and set a value between 01 and 50 s (at 00 the
►
delay time is not active)
9.5.3 Setting of the error behaviour of the outputs
Select [FOU1] and set the value:
►
[On] = Output 1 switches ON in case of a fault
-
[OFF] = Output 1 switches OFF in case of a fault
-
Select [FOU2] and set the value:
►
[On] = The analogue signal goes to the upper limit value (210 mA /
-
106 V)
[OFF] = The analogue signal goes to the lower limit value (35m A /
-
0 V)
9.5.4 Setting of the switching logic for OUT1
Select [P-n] and set [PnP] or [nPn]
►
9.6 Service functions
9.6.1 Reading of the min/max values for the system temperature
Select [HI] or [LO], briefly press [Set]
►
[HI] = maximum value, [LO] = minimum value
Delete memory:
Select [HI] or [LO]
►
Press [Set] and keep it pressed until [----] is displayed
►
Press [Mode/Enter] briefly
►
9.6.2 Reset of all parameters to factory setting
Select [rES]
►
Press [Set] and keep it pressed until [----] is displayed
►
Press [Mode/Enter] briefly
►
We recommend taking down your own settings in the table before carrying
out a reset (→ 13 Factory setting).