9 Parameter setting
During parameter setting the unit remains in the operating mode It continues its
monitoring function with the existing parameters until the parameter setting has
been completed
9.1 General parameter setting
3 steps must be taken for each parameter setting:
1
Selection of the parameter
Press [Mode/Enter] until the re-
►
quested parameter is displayed
.
���������� ���
2
Setting of the parameter value
Press [Set] and keep it pressed
►
Current setting value of the param-
>
eter flashes for 5 s
After 5 s: Setting value is changed:
>
incrementally by pressing the button
once or continuously by keeping the
button pressed
���������� ���
Numerical values are incremented continuously For reducing the value: Let the dis-
play move to the maximum setting value Then the cycle starts again at the minimum
setting value
3
Acknowledgement of the parameter
value
Press [Mode/Enter] briefly
►
The parameter is displayed again
>
The new setting value is stored
���������� ���
Setting of other parameters
Start again with step 1
►
Finishing the parameter setting
Press [Mode/Enter] several times until the current measured value is displayed or wait
►
for 15 s
The unit returns to the operating mode
>
If [SLoc] is displayed when attempting a modification of a parameter value, the sensor is
•
locked via software This locking can only be removed via a parameter setting software
In case of parameter setting with the user interface of the ifm Container program, the
•
values can be directly entered in the specified fields
For IO-Link parameter setting → device-specific parameter lists at: www.ifm.com → Select
•
your country → Data sheet direct: