10
8.2 Response times
Response time on safety request
(removal from the enable zone)
≤ 1 ms
Response time when approaching the enable zone
(enable time)
≤ 1 ms
Risk time / response time for safety-related faults
≤ 20 ms
Simultaneity of switching on and off of the outputs in case of a safety
request
≤ 1 ms
Duration of switch-off test pulses
≤ 1 ms
8.3 LED display
LED
status
Operating status
Outputs
A1
(OSSD)
A2
(OSSD)
Signal
Power
no voltage supply
both outputs switched off
0
0
Signal
Power
undervoltage
1
0
0
0
Signal
Power
overvoltage
both outputs switched off
0
0
Signal
Power
damping element at safe
switch-off distance from the
sensor (≥ 7 mm)
both outputs switched off
0
0
Signal
Power
sensor error
(→ 11 Troubleshooting)
one output or both
outputs switched off
0
1
0
1
0
0
Signal
Power
damping element in the
enable zone
both outputs enabled
1
1
damping element in the
close zone
output A2 is switched off
1
0