DP module 7: Command channel
Module 7, command 23dec (17hex):
address slave
8-21
8.20
Module 7, command 23
dec
(17
hex
):
address slave
IMPORTANT:
The controllere must be in the configuration mode.
Structure
Request of DP master
Bit
MM = master no. (1…2)
Byte
7
6
5
4
3
2
1
0
1
0 0
17
hex
X = slave type (0…1)
0 = standard / A slave
1 = B slave
2
MM X
SSSSS
SSSSS = slave no. (0…31
dec
)
3
new slave address
4
0
not used *)
Response from controllere
Bit
Byte
7
6
5
4
3
2
1
0
1
D7 D6
17
hex
2
copy of the request
D6 = command code
D7 = error code
→
page
, table at the bottom
3
copy of the request
4
error message
Error codes
→
page
Example: address slave 2B on AS-i master 1 to 7B
Request of DP master
Byte no.
Value [hex]
Description
1
17
17 = command 23
2 62
(slave no.
2
)
+ (master no.
1 * 64
)
+ (
32
, if B slave)
= 98
dec
=
62
hex
3
07
new slave address 7B
4
00
not used *)
Response from controllere in case of an error
Byte no.
Value [hex]
Description
1
17
copy of the request
2
62
copy of the request
3
07
new slave address
4 14
Error codes
→
page
here: error: master is in the wrong operating mode
*)
IMPORTANT:
For the query read only the required bytes. Unused bytes can contain information of
previous queries.
Summary of Contents for Ecomat 300 AC1355
Page 8: ...8 15 Terms abbreviations 15 1 16 Index 16 1 ...
Page 12: ...On this manual Overview where is what 1 4 ...
Page 14: ...Safety instructions Functions and features 2 2 ...
Page 16: ...System requirements Required accessories 3 2 ...
Page 18: ...Getting started Set up Profibus DPV1 4 2 ...
Page 24: ...Menu Main menu Fieldbus Setup 6 4 ...
Page 52: ...Set up Finish set up 7 28 ...
Page 238: ...Technical data Profibus DP interface 13 2 ...
Page 246: ...Terms abbreviations 15 6 ...