6
4.1.1 "AUX" voltage supply
►
Connect the device to the voltage supply using an M12 connection cable .
3
1
2
4
5
Pin
Connection
1
24 V DC
2
not used
3
0 V
4
not used
5
not used
4.1.2 Field bus connection EtherNet/IP Port 1 / Port 2
►
Connect the device to an EtherNet/IP master using a suitable M12 Ethernet connection cable .
1
2
3
4
Pin
Connection
1
TD+
2
RD+
3
TD-
Note: screened
connection cable
required
4
RD-
Factory setting of the Ethernet parameters
The following values are preset on delivery of the device:
Parameters
Factory setting
IP address
192 .168 .0 .79
Gateway address
192 .168 .0 .100
Subnet mask
255 .255 .255 .0
Auto-negotiation
on
DHCP
off
The settings can be changed via the webserver of the device or via the TCP/IP interface object of the
EtherNet/IP bus .
4.1.3 Process connections "IO-1 ... IO-4"
Each process connection can be used as input/output to IEC 61131 or for connection of an RFID read/
write head type ANT51x/ANT41x .
3
1
2
4
5
Pin
Connection
1
L+
2
switching input (I/Q)
3
L-
4
switching output (C/Qo) or
input (C/Qi)
5
not used
The evaluation unit has to be disconnected before field units are connected .
Please note that the total current consumption of the device must not exceed the value of 3 A .
You can find information about the matching read/write heads on our website at:
www .ifm .com