9.11.1
Coding of the channel configuration
All 4 channels IO-1 . . .IO-4 of the evaluation unit are configured identically .
The following table shows the coding of the 8 bytes per channel:
Byte
Content
Remark
N+0
(CN)
Channel IO-x number
[
01h
…
04h
]
Used to identify the channel within the configuration assembly
102
N+1
(MO)
Module identifier
01h
für
INACTIVE
(20 Bytes In/Out)
02h
für
INPUT
(20 Bytes In/Out)
03h
für
OUTPUT
(20 Bytes In/Out)
0Bh
für
RWH_RW
(20 Bytes In/Out)
Default: INACTIVE
Channel is deactivated
Channel is configured as IEC61136 input
Channel is configured as IEC61136 output
Channel is configured as communication channel to the read-/
write head
N+2
DH
Data hold time
[
00h … FFh
] in 10 x milliseconds
Default: 0 ms
Hold time I/Q, UID
N+3
(
TL
)
Transponder data block length
[
1,2,4,8,16,32,64,128,255
]
Default: 4 bytes
-
N+4
(
OL
)
Overload detection
[
01h=on
/
00=off
]
Default : on
Overload at output L+ > 500 mA
N+5
(
OC
)
Overcurrent detection
[
on/off
]
Default : on
Overcurrent at output
C/Qo > 300 mA
N+6
(
RU
)
Read of UID edge controlled
[
on/of
f]
Default : off
Edge-controlled reading of the UID via bit RD in the controlword
of the module RWH_RW .
N+7
(-)
Reserved
for future use
-
Table 10: Coding of the channel configuration
Setting the offsets off the channels IO-1 … IO-4
Description
Byte offset within the configuration assembly
Channel 1
N=0
Channel 2
N=8
Channel 3
N=16
Channel 4
N=24
9.11.2 Coding of the evaluation unit parameters
Byte
Content
Remark
32
Failsafe mode [ on/off ]
Default: off
Failsafe mode = off:
The IO-Channel is deactivated if no connection to the Ethernet/
IP scanner is established .
Failsafe mode = on:
The IO-Channels remain activated and the outputs keep the
last received state if no connection to the Ethernet/IP scanner
is established .
33 . . 39
Reserved .
-
40 . . 63
Reserved
Table 11: Coding of the evaluation unit parameters