UK
Operating instructions AX460
35
9.16 Analog Out Menu
In this menu the basic settings for the analogue output are defined� This function is
only available for the devices DX2043 and DX2053�
ANALOG SOURCE
This parameter defines the source for preselection for the analogue output�
The totalization depends on the selected operating mode
INPUT 1
Source is input 1
INPUT 2
Source is input 2
LINKAGE 1 – 2
The source is the result of the linking of input 1 and input 2
INPUT 1 TOTAL
Source is input 1 with totalization
INPUT 2 TOTAL
Source is input 2 with totalization
LINKAGE TOTAL
The source is the result of the linking of input 1 and input 2 with
totalization
IO LINK VALUE 1
The PDout value 1 sent by the IO-Link master is the source for
preselection
IO LINK VALUE 2
The PDout value 2 sent by the IO-Link master is the source for
preselection
MINIMUM VALUE 1
Source is input 1
MAXIMUM VALUE 1
Source is input 1
MINIMUM VALUE 2
Source is input 2
MAXIMUM VALUE 2
Source is input 2
ANALOG FORMAT
This parameter defines the output characteristic� For the output format (-10 … +10 V), the polarity of the
output follows the algebraic sign in the display (only in the operating mode COUNTER)�
The analogue output is proportional to the display value�
-10…10V
-10 … +10 V
0…20MA
0 ��� 20 mA
4…20MA
4 ��� 20 mA
ANALOG START
With this parameter, the start value of the analogue gain can be set� The start value determines at which
display value the analogue output has a gain of 0 V or 0 / 4 mA�
-99999999
Lowest possible start value
0
Default value
+99999999
Highest possible start value
ANALOG END
With this parameter, the end value of the analogue gain can be set� The end value determines at which
display value the analogue output has a maximum value of +/- 10 V or 20 mA�
-99999999
Lowest possible final value
10000
Default value