Remote I/O module 16 DI
AL4103
43
u
Open the [Device view].
w
The [Device overview] tab displays the device structure.
u
Click on the module [PN_IO] (slot 1, subslot X1).
w
The [General] tab displays general configuration options.
u
Select [Advanced options] > [X21 [X1 P1 R]] > [Port options].
u
In the list [Transmission rate / duplex], select the value [TP 100Mbps full duplex]. The selected
value must match the transmission rate of the network partner.
u
Disable the option [Enable autonegotiation].
w
The transmission rate of Ethernet port 1 is permanently set.
u
Repeat steps for Ethernet port 2 ([X22 [X1 P2 R]]).
w
The transmission rate of Ethernet port 2 is permanently set.
w
The Fast Startup function is activated for PROFINET IO ports.
9.3.4 Configure input filters
u
Observe the notes on input filters: Digital input filters (
The input filters are configured via the following module:
•
The module is permanently assigned to slot 1.
Each digital input on pin 2 and pin 4 of the ports has a filter. Each of these filters can be configured
separately.
Available parameters per input filter:
•
debounce time
•
hold time
•
hold level
•
signal inversion
Requirements:
ü
Device is integrated in PROFINET project.
u
Open the [Device view].
w
The [Device overview] tab displays the device structure.
u
Click on the module [8x2 DI + Qualifier] (slot [1]).
w
The [Properties] view appears.
w
The [General] tab displays the properties of the module.
w
[Module parameters] provides access to parameters of the digital inputs.
u
Set the parameters of the input filters.
u
Save the project.