The filters of the digital inputs are configured.
w
The changed configuration will be activated the next time the application is downloaded to the
device.
9.3.5 Configure counter modules
u
Observe the notes on counter modules: Counters (
The counter modules are configured via the module [Counter Module] and its submodules:
•
•
•
•
The module [Counter Module] needs to be assigned to slot 2 manually. Subsequently, a counter
submodule can be assigned to each port via the respective subslot. The counter submodule
determines the operating mode of the counter.
Each counter module can be configured separately.
Available parameters of the counter submodules:
•
event messages of the main counter
•
event messages of the batch counter
•
threshold CT of the main counter
•
threshold CTb of the batch counter
•
function of pin 2 of the port
•
instance for selecting the counting direction (only with CTDIR operating mode)
Requirements:
ü
Device is integrated in PROFINET project.
u
Open the [Device view].
w
The [Device overview] tab displays the device structure.
u
In the hardware catalogue under [Modul] > [Counter], select the module [Counter Module] and
move it to slot 2 using drag & drop.
w
The counter module is assigned to the device.
w
The device overview displays the port designations assigned to the slot.
w
The hardware catalogue displays the available submodules.
u
In the hardware catalogue under [Submodule] > [Counter], select the desired counter submodule
and move it to a free subslot of the port using drag & drop.