![background image](http://html2.mh-extra.com/html/ifm/ac6000/ac6000_operating-instructions-manual_3883155069.webp)
IO-Link Master with AS-Interface Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
69
>
Command response
52129
Byte
Bit
7
6
5
4
3
2
1
0
0
0x00
1
Block Counter
2
Command status (
→
list "Diagnostic codes")
3
0x00
4...160
ignored
Diagnostic codes:
0x01
OK
0x04
Blocked Port - another acyclic access is still active
0x07
Wrong Target ID (wrong Port number)
0x08
Invalid length (wrong input parameter length)
0x09
Wrong parameter (value of a parameter not in proper range)
0x0A
Wrong Block ID