IO-Link Master with AS-Interface Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
86
>
Command response
52153
Byte
Bit
7
6
5
4
3
2
1
0
0
0x00
1
Block Counter
2
Command status (
→
list "Diagnostic codes")
3
Data Length
4
ignored / Error Code
5
ignored / Additional Error Code
6...160
ignored
Legend:
[Data Length]
Length of the return data (number of bytes n)
8 bits
0x00
no error codes
0x02
Error code and additional
error code
[Error Code]
Error code
8 bits
0x80
Error in IO-Link device
[Additional Error Code] additional error code
8 bits
→
IODD of the IO-Link device
Diagnostic codes:
0x01
OK
0x04
Blocked Port - another acyclic access is still active
0x07
Wrong Target ID (wrong Port number)
0x08
Invalid length (wrong input parameter length)
0x0A
Wrong Block ID
0x0B
Error - for additional information see data field