IO-Link Master with AS-Interface Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
28
>
9.4
Configuring IO-Link ports
59311
The configuration of an IO-Link port consists of the following parameters:
•
Operating mode (IO-Link, digital input, digital output, disabled)
•
Cycle time of the data transmission between the IO-Link master and the IO-Link device
•
Data storage of the IO-Link device configuration for automatic recovery
•
Device validation for connected IO-Link devices (validation ID)
•
Vendor and device ID for active device validation (Vendor ID / Device ID)
•
Fail-safe values in case the AS-i connection is interrupted
Available commands:
Name
Description
Reference
0x03: Reading IO-Link port
configuration
Read current configuration of all IO-Link ports
0x03: Read IO-Link Port Configuration
(
→
0x02: Write IO-Link Port
Configuration
Write the configuration of all IO-Link ports
0x02: Write IO-Link Port Configuration
(
→
0x09: Set IO-Link Failsafe Data Set fail-safe values
0x09: Set IO-Link Failsafe Data
(
→
0x01: Reading IO-Link Port
Configuration Errors
Read configuration errors of the IO-Link ports
0x01: Read IO-Link Port Configuration
Errors
(
→
>
9.4.1
Note: Device validation and data storage
59312
The user can choose how the IO-Link ports are to behave with regard to the device validation and the
storage / recovery of parameter data of the connected IO-Link device.
The following options are available:
Option
Validation of the IO-Link
device
Storage of the parameter values Recovery of the parameter
values
[No check and clear] no
no
no
[Type compatible
V1.0 device]
yes, test the compatibility with
IO-Link standard V1.0
no
no
[Type compatible
V1.1 device]
yes, test the compatibility with
IO-Link standard V1.1
no
no
[Type compatible
V1.1 device with
Restore]
yes, test the compatibility with
IO-Link standard V1.1 and
identity of design (vendor ID
and device ID)
yes, automatic storage of the
parameter values; changes of the
current parameter values will be
stored
yes, recovery of the parameter
values when connecting an
identical IO-Link device with
factory settings
[Type compatible
V1.1 device with
Restore]
yes, test the compatibility with
IO-Link standard V1.1 and
identity of design (vendor ID
and device ID)
no, there is no automatic storage
changes of the current parameter
values will not be stored
yes, recovery of the parameter
values when connecting an
identical IO-Link device with
factory settings
The options only apply if the IO-Link port is in the operating mode "IO-Link".
For options [Type compatible V1.1 device with Restore] and [Type compatible V1.1
device with Restore]: If the vendor ID and device ID are changed in the online mode, the data
memory will be deleted and a new backup of the parameter values of the connected IO-Link
device will be created in the IO-Link master.