5.1.1  Restore the factory setting (address both slaves to 0) to AC2489

Recommendation: 
Use the addressing unit AC1154 to restore the factory settings.

When AS-i masters are used and „automatic addressing“ is activated restoring the 
factory settings is reversed.

Using the addressing unit AC1154 the factory settings of the module are restored 
by writing a 0 to ID1 of the second slave (factory setting ID1 = 2). 
When the factory settings are restored via the AC1154 the status message [F3] is 
displayed. 

 

► Press mode button once to close the status message.

 

► Operating mode ID2 appears.

 

► Then press the mode button as long as the addressing mode ADDR is visible 

to display the factory settings (address 0).

6  Settings

The AC2488 module occupies only one slave address. The data of the module is 
in the analogue range.

6.1  Data bits and value range CTT3 in the M4 Controller

e

 and 

AC14xx to AC2488

binary IN1 (D0)
binary IN2 (D1)
binary IN3 (D2)
binary IN4 (D3)
binary IN5 (D4)
binary IN6 (D5)
binary IN7 (D6)
binary IN8 (D7)

analogue IN 1  D7...D0    (byte 1)   byte 0 

 

 

analogue IN 2  byte 3                        byte 2 

 

 

analogue IN 3  D7...D0    (byte 5)   byte 4
analogue IN 4  byte 7                        byte 6

slave address 2A