3

UK

2  Functions and features

•  AC2488: 8 inputs CTT3 (AS-i profile S-7.A.A) / AS-interface version 3.0 / 

master profile M4 / extended addressing mode: yes / maximum number of 
modules per master: 62

•  AC2489: 2x4 inputs (AS-i profile 2x S-0.A.E) / AS-interface version 3.0, 

backwards compatible / master profile M3 or M4 / extended address mode: 
yes / maximum number of modules per master: 31 (2 independent A/B slaves 
per module)

3  Installation

 

► Disconnect power before installation.

 

► For installation choose a flat mounting surface.
The entire bottom of the module must lie flat on the mounting surface.

 

► Fix the module onto the mounting surface using M4 screws and washers. 

4  Electrical connection

The unit must be connected by a qualified electrician.
The national and international regulations for the installation of electrical equipment 
must be adhered to.

 

► Disconnect the installation from power and connect the unit.
To ensure the protection rating: 

 

► Connect the plugs of the sensors to the M8 sockets.

 

► Tighten firmly, recommended tightening torque 0.3...0.5 Nm. 

 

► Cover the unused sockets with the enclosed protective caps.

 

► Tighten firmly, recommended tightening torque 0.3...0.5 Nm.